AKO 14212 Instrukcje - Strona 2

Przeglądaj online lub pobierz pdf Instrukcje dla Kontroler temperatury AKO 14212. AKO 14212 2 stron. Up to three relays and two probes

AKO 14212 Instrukcje
Level 3
Values
- To DISPLAY the CURRENT VALUE of any parameter, select the required one and press
+
keys simultaneously. Once it is displayed, you can CHANGE VALUE, pressing
key.
- Press
+
keys simultaneously to ACCEPT THE NEW. The programming returns to
LEVEL 2 PARAMETERS.
CURRENT
PASSWORD
TEMPERTATURE
IF PROGRAMMED
SIMULTANEUSLY
10 Sec.
IF L5=0
SIMULTANEUSLY
SIMULTANEUSLY
PASSWORD
ENTER
DISPLAY
REQUEST
PASSWORD
PASSWORD
REMARK: If no key is pressed for 25 seconds in either of the previous steps, the controller
will automatically return to the CURRENT TEMPERATURE display status without modifying
any of the parameters values.
6- Description of parameters and messages
Values in the Def. column are factory-set.
Level 1
Menus and Description
rE Level 2
REFRIGERATION control (Compressor)
Level 3
Description
C0 Sensor 1 calibration (Offset)
C1 Sensor 1 differential (Hysteresis)
Set Point upper limit
C2
(It cannot be set above this value)
Set Point lower limit
C3
(It cannot be set below this value)
Compressor protection delay type:
C4
0=OFF/ON ((From the last switch-off) 1=ON (At switch-on)
Protection delay time
C5
(Value for the option selected in parameter C4)
"COOL" (Compressor) relay time in ON
C7 in case of faulty sensor 1
(If C7=0 and C8≠0, the relay will always be OFF disconnected)
"COOL" (Compressor) relay time in OFF
C8 in case of faulty sensor 1
(If C8=0 and C7≠0, the relay will always be ON connected)
EP Exit to Level 1
dEF Level 2
DEFROST control
Level 3
Description
d0 Defrost frequency (Elapsed time between 2 starts)
d1 Defrost maximum duration
Type of message during defrost:
(0=Current temperature display)
d2
(1=Defrost start temperature display)
(2=Display dEF message)
d3 Message maximum duration (Time added at the end of defrost)(min.)
Defrost final temperature by sensor 2
d4
(If programmed in P4) In 2 relay versions, it operates if P6=0
Defrost start-up on equipment switch-on:
d5
(0=NO, first defrost according to d0) (1=YES, first defrost according to d6)
d6 Defrost start-up delay on equipment switch-on
Defrost type: (0=Electric heat)
d7
To defrost by air in 2 relays, parameters P6 and F3 should be programmed
d8 Time calculation between defrost periods:
(0=Total real time)
(1=Compressor operation sum)
Drip time, compressor stop and FAN/R2
d9
relay off when defrost ends
EP Exit to Level 1
FAn Level 2
FANS control (Evaporator)
Level 3
Description
F0 Fans stop temperature by sensor 2
(If programmed in P4)
F1 Sensor 2 differential
Stop fans, when compressor stops?:
F2
In 2 relays versions, R2 operates if P6=1
F3 Fans status during defrost:
(0=Off)
(1=On)
Start-up delay after defrost
F4
(Operates if it is higher than d9)
EP Exit to Level 1
Av. Roquetes, 30-38 | 08812 Sant Pere de Ribes | Barcelona | España
Tel. (34) 938 142 700 | Fax (34) 938 934 054 | e-mail: [email protected] |
Apartado (P.O. Box), 5 | 08800 Vilanova i la Geltrú | Barcelona | España
LEVEL 1
LEVEL 2
LEVEL 3
MENUS
PARAMETERS
VALUES
SIMULTANEUSLY SIMULTANEUSLY
SIMULTANEUSLY
CURRENT
NEW
VALUE
VALUE
EXIT
EXIT TO
PROGRAMMING
LEVEL 1
Values Min. Def. Max.
(ºC/ºF) -20.0 0.0 20.0
(ºC/ºF) 0.1 2.0 20.0
(ºC/ºF)
C3 99.9 99.9
(ºC/ºF) -50.0 -50.0 C2
0
0
(min.)
0
0
(min.)
0
10
(min.)
0
5
Values Min. Def. Max.
(h.)
0
6
(min.)
0
30
0
2
0
5
(ºC/ºF) -50.0 8.0 99.9
0
0
(min.)
0
0
(1=Hot gas by-pass)
0
0
0
0
(min.)
0
1
Values Min. Def. Max.
(ºC/ºF) -50.0 4.0 99.9
(ºC/ºF) 0.1 2.0 20.0
0
0
0
0
(min.)
0
3
AL Level 2
ALARM control (Visual)
Level 3
Description
or
Configuration of temperature alarms
A0
(0 = Relative to SP)
A1 Maximum alarm in sensor 1
A2 Minimum alarm in sensor 1
Temperature alarm delay in the start-up
A3
(If programmed in A1, A2)
A4 Temperature alarm delay from the end of a defrost
A5 Temperature alarm delay from the
moment at which they should operate due to temperature
A8 Signals if defrost ends due to maximum time:
(0=Led DT OFF)
A10 Differential Alarms Temperature A1 and A2
EP Exit to Level 1
CnF Level 2
GENERAL STATUS
Level 3
Description
P1 Delay of all functions on power supply switch on
P2 Allocation of password to Set Point:
(0=Without allocation) (1=With allocation of L5 password)
P3 Initial parameters: (1=YES, configure to "Def" and exit programming)
P4 Connected sensors: (1=Sensor 1) (2=Sensor 1 + Sensor 2)
P5 Address for units with communication
P6 Relay 2 (F2) function in 2 relay versions:
(0=Defrost)
(1=Fans control)
Temperature display mode:
P7 (0=Integers in ºC)
(2=Integers in ºF)
P8 Sensor to be displayed: (1=Sensor 1)
EP Exit to Level 1
tid Level 2
ACCESS AND INFORMATION control
Level 3
Description
L5 Access password to parameters and information
L6 Parameters transfer: (0=Disabled) (1=Send) (2=Receive)
PU Program version (Information)
EP Exit to Level 1
EP Exit programming
REMARK: When time parameters are modified, the new values are applied when the current
cycle is completed. In order for it to have an immediate effect, switch the controller off and
then on again.
MESSAGES
Password request to enter programming parameters
PA
or SET POINT
1
It indicates defrosting is being carried out. In order to display "dEF"
dEF during defrosting, it is essential that parameter d2
is set to option 2.
99
Flashing with temperature - Sensor 1 temperature exceeds the parameter
AH
programmed in A1
99
Flashing with temperature - The Sensor 1 temperature is lower than the
AL
parameter programmed in A2
E1 Sensor 1 failure (Open circuit, crossed, temp.> 110ºC or temp.<-55ºC)
99
E2 Sensor 2 failure (Open circuit, crossed, temp.> 110ºC or temp.<-55ºC)
ES Incorrect sensor configuration (See P4, P8)
EE Memory failure
99
7- Parameters transfer
99
Portable server
AKO-14918 portable server, with no power supply, in
2
which parameters programmed in a powered controller
can be copied by transfer. Parameters can be transferred
99
again from the server to other identical powered con-
trollers.
To transfer parameters, other servers are available for
controllers that should be programmed identically in
1
high quantity without power supply.
99
1
8- Maintenance
1
Clean the controller surface with a soft cloth, soap and water. Do not use abrasive deter-
99
gents, petrol, alcohol or solvents.
9- Warnings
The use of the unit without observing the manufacturer's instructions may alter its safety
qualification.
To ensure correct operation of the apparatus, only NTC type probes supplied by AKO should
be used.
1
Between -40 ºC and +20 ºC, when the probe is extended up to 1.000 m with minimum
0,5 mm
2
cable, deviation will be less than 0.25 ºC (Probe extension cable ref. AKO-15586).
1
(*) The intensity specified for each relay is its maximum individual value; if more
than one is connected, the intensity of the addition (COMPRESSOR + DEFROST
99
+ FAN) must not exceed the total maximum intensity specified in the rating
plate.
AKO ELECTROMECÀNICA, S.A.L.
www.ako.com
Nos reservamos el derecho de suministrar materiales que pudieran diferir levemente de los
descritos en nuestras Hojas Técnicas. Información actualizada en nuestra web: www.ako.com.
Values Min. Def. Max.
(1 = Absolute)
(ºC/ºF)
(ºC/ºF) -50.0 -50.0 A1
(min.)
(min.)
(min.)
(1=Led DT ON)
(ºC/ºF) 0.1 1.0 20.0
Values Min. Def. Max.
(min.)
(1=One decimal in ºC)
(3=One decimal in ºF)
(2=Sensor 2)
Values Min. Def. Max.
AKO-14918
Transfer
0
0
1
A2 99.9 99.9
0
0
120
0
0
99
0
30
99
0
0
1
0
0
99
0
0
1
0
0
1
1
1
2
0
0
126
0
0
1
0
1
3
1
1
2
0
0
99
0
0
2
Power supply
Programming