3.2 Panel Mounting (maximum panel thickness: 3 mm)
- Remove cover T from the equipment (Fig.1).
- Open the equipment and separate the front part of the housing (Fig.2).
- Replace the gasket installed in the front panel with panel mounting gasket, bearing in mind its correct position.
- Make a hole in the panel of the specified size (214 x 214 mm). (Fig.4)
- Drill the holes needed for the cable entry glands using the pre-stamped centres on the sides of the housing for
guidance.
- Finish drilling holes G, J with a 4 mm bit (Fig.3).
- Fit the cable glands in the equipment.
- Insert the cables into the glands.
- Fix the front onto the housing, through the panel, connect the battery, close the front and tighten the 44 mm bolts
through holes D, F, G, J (Fig.3).
- After connecting the cables as shown in the wiring diagram, close cover T, and insert and tighten screws A, C (Fig.1).
FIG. 1
3.3 Installing the push button
The push button must be installed inside the cold room, in a visible location at a height of no more than 125 cm. The
equipment must be connected as shown in the wiring diagram described below.
Press gently
Fixing holes for universal
flush-mounted box
3.4 Connection
Ensure the batteries are connected before switching on the equipment.
Always disconnect the power supply before making any connections.
The power supply circuit should be connected with a minimum 2 A, 230 V, switch located close to the unit. Power supply
cables should be H05VV-F or H05V-K. The gauge will depend on local regulations, but should in no case be less than
1 mm2.
Cables for connecting the relay contact should have a sufficient gauge for the equipment to be connected.
10
222,1 mm
140 mm
FIG. 2
FIG. 3
35
214 mm
PANEL
CUT-OUT
FIG. 4
Max. Ø 3,7
125,5
171