AKO AKO-14220 Instrukcje instalacji - Strona 2

Przeglądaj online lub pobierz pdf Instrukcje instalacji dla Kontroler AKO AKO-14220. AKO AKO-14220 2 stron.

AKO AKO-14220 Instrukcje instalacji
6 - Table of parameters and messages
Def. column shows factory-set default parameters. Those marked with
by application"). If not indicated otherwise, the temperature values are in ºC. (Equivalent velues in °F)
AKO-D14312, AKO-D14320, AKO-D14323
AKO-D14212, AKO-D14220, AKO-D14223
AKO-D14112, AKO-D14123-2
Level 1
Menus and description
rE
Level 2
Control
Level 3
Description
Temperature Adjustment (Set Point)
SP
(limits depending on probe type)
C0
Calibrating probe 1 (Offset)
C1
Probe 1 differential (Histeresis)
Upper blocking of the set point
C2
(cannot be set above this value)
C3
Lower blocking of the set point (cannot be set below this value)
Type of delay for protection of the compressor:
C4
0=OFF/ON (since the last disconnection);
1=OFF-ON/ON-OFF (since the last shut-down /start-up)
C5
Protection delay time (value of the option selected in parameter C4)
Status of COOL relay with probe fault
C6
0=OFF; 1=ON; 2=Average based on last 24 hours prior to probe fault;
3=ON-OFF as prog. C7 and C8
Time relay ON in case of faulty probe
C7
(If C7=0 and C8¹0, the relay will always be OFF deenergised)
Time relay OFF in case of fault of probe 1
C8
(If C8=0 and C7¹0, the relay will always be ON energised)
C9
Maximum duration of fast freezing mode. (0=off)
Change set point (SP) in fast freezing mode, when it reaches this point (SP + C10)
C10
returns to normal. (SP+C10 ³ C3) (0=OFF)
Length of inactivity at digital input to activate ECO mode
C11
(Only if P10 or P11=1 and P0=0) (0=OFF)
C12
Change set point (SP) in ECO mode (SP+C12 C2) (0=off)
EP
Exit to Level 1
dEF
Level 2
DEFROST Control (if P0=0 Direct, Cold)
Level 3
Description
d0
Defrost frequency (Time between two starts)
d1
Maximum defrost duration (0=defrost deactivated)
Type of message during defrost:
d2
0=Current temperature; 1=Temperature at start of defrost; 2=Display dEF message
d3
Maximum duration of message (time added at the end of the defrost)
d4
Defrost end temperature (probe 2) (If P4 ¹ 1)
Defrost on equipment start-up
d5
0=NO, First defrost as per d0, 1=YES, First defrost as per d6
d6
Defrost start delay on equipment start-up
Defrost type: 0=Resistors, 1=Inverted cycle,
d7
(In two-relay equipment, P6 must be programmed to zero)
Calculated time between defrost periods:
d8
0=Total actual time; 1 =Sum of times the compressor is on
d9
Drip time at end of defrost (compressor and fans off) (if P4 ¹ 1)
EP
Exit to Level 1
Level 2
FAN control (Evaporator)
FAn
In 2-relay models P6 must be set to 0
Level 3
Description
F0
Fan shut-down temperature as per probe 2 (if P4 ¹ 1)
F1
Probe 2 differential (If P4 ¹ 1)
F2
Stop fans when stopping compressor 0=No, 1=Yes
F3
Fan status during defrost: 0=Off; 1=On
Starting delay after defrost (if F3=0)
F4
Will only operate if it is higher than d9
Stop fans on opening the door 0=No, 1=Yes
F5
(Requires a digital input configured as port P10 or P11=1)
EP
Exit to Level 1
AL
Level 2
ALARMS control (visual)
Level 3
Description
A0
Configuration of temperature alarms: 0=Relative to SP; 1=Absolute
A1
Maximum alarm probe 1 (must be greater than SP)
A2
Minimum alarm probe 1 (must be less than SP)
A3
Temperature alarm delay during start-up
A4
Temperature alarm delay after completion of a defrost
A5
Temperature alarm delay after reaching the value of A1 or A2
External alarm / Severe external alarm delay when receiving digital input signal
A6
(P10 or P11=2 or 3)
Desactivation delay of the external alarm / Severe external alarm when the
A7
signal of the digital input disappears (P10 or P11=2 or 3)
A8
Show warning if defrost is terminated by time-out 0=No, 1=Yes
Alarm relay polarity 0=Relay ON in alarm (OFF no alarm)
A9
1=Relay OFF on alarm (ON with no alarm)
A10
Temperature Alarm Differential (A1 and A2)
A12
Door open alarm delay (if P10 or P11=1)
EP
Exit to Level 1
CnF
Level 2
General status
Level 3
Description
P0
Type of operation 0=Direct, Cold;1=Inverted, Heat
P1
Delay of all functions on receiving electrical power
Access code (password) functions
P2
0=Inactive; 1=Block access to parameters; 2=Keyboard lock
Selection of type of input
P4
1=1 probe + 2 digital inputs, 2=2 probes +1 digital input
Address (only systems with built-in communications)
P5
Configuration of AUX relay
P6
1=defrost
2=Alarm
Temperature display mode
0=Whole in ºC
P7
2=Whole in ºF
Probe to be displayed (as per parameter P4)
P8
0=visualization of all the probes in sequence; 1=Probe 1; 2=Probe 2; 3=Probe 3 (1)
P9
Selection of probe type 0=NTC; 1=PTC
*
are variable parameters depending on the application chosen in the wizard or the P3 parameter (see table "Default parameters
Values Min. Def. Max.
With NTC
-50
(ºC/ºF)
(-58ºF)
With PTC
(ºC/ºF)
-20.0
0.0
(ºC/ºF)
0.1
2.0
99
With NTC
(210ºF)
(ºC/ºF)
C3
With PTC
-50
-50
(ºC/ºF)
(-58ºF)
(-58ºF)
0
0
(min.)
0
0
0
2
(min.)
0
10
(min.)
0
5
(h.)
0
24
-50
(ºC/ºF)
0
(-58ºF) C3-SP
(h.)
0
2
(ºC/ºF)
£
0
2
Values Min. Def. Max.
(h.)
0
(min.)
0
0
2
(min.)
0
5
-50
8
(ºC/ºF)
(-58ºF)
(46ºF)
0
0
(min.)
0
0
0
0
0
0
(min.)
0
1
Values Min. Def. Max.
-50
(ºC/ºF)
(-58ºF)
(ºC/ºF)
0,1
2,0
0
1
0
(min.)
0
3
0
0
Values Min. Def. Max.
0
0
99,9
With NTC
(211ºF)
(ºC/ºF)
A2
With PTC
-50
-50
(ºC/ºF)
(-58ºF)
(-58ºF)
(min.)
0
(min.)
0
0
(min.)
0
30
(min.)
0
0
(min.)
0
0
0
0
0
0
(ºC/ºF)
0,1
1,0
(min.)
0
2
Values
Min. Def. Max.
0
(min.)
0
0
0
0
1
1
0
1
0=Fan (only 2-relay equipment)
0
3=Light
1=One decimal in ºC
0
1
3=One decimal in ºF
1
1
0
0
AKO-D14312, AKO-D14320, AKO-D14323
AKO-D14212, AKO-D14220, AKO-D14223
AKO-D14112, AKO-D14123-2
Level 1
Menus and description
Configuring digital input 1
0= Off
P10
3=Severe external alarm 4=Slave defrost
99
·
·
·
(210ºF)
6=Act. Fast Freezing
150
9=Act. ECO mode by switch
-
·
· ·
(302ºF)
Configuring digital input 2
·
·
·
20.0
0= Off
·
·
·
20.0
P11
3=Severe external alarm 4=Slave defrost
99
·
· ·
6=Act. Fast Freezing
(210ºF)
9=Act. ECO mode by switch
150
-
·
· ·
P12
Digital input polarity 1 0=Energised on closed contact, 1=Energised on open contact
(302ºF)
P13
Digital input polarity 2 0=Energised on closed contact, 1=Energised on open contact
·
· ·
C2
P19
Lights in ECO Mode (P6=3) 0=ON; 1=OFF
EP
Exit to Level 1
·
· ·
1
tid
Nivel 2
Access and information control
Level 2
Level 3
Nivel 3
·
· ·
120
L5
Access code (Password)
PU
Program version (Information)
·
· ·
3
Pr
Program revision (Information)
EP
Exit to Level 1
EP
Exit Programming
·
· ·
120
·
· ·
WARNING: The default parameters by type of application have been
120
defined for the most common applications. Check that these parame-
·
· ·
48
ters are suitable for your installation.
·
· ·
·
· ·
DEFAULT SETTINGS BY APPLICATION (InI)
24
1
·
· ·
C2-SP
Multipurpose
·
· ·
SP
2 (35,6ºF)
d0
4
d1
20
·
· ·
96
F0
8 (46ºF)
·
· ·
255
F3
1
·
· ·
2
P0
0
·
· ·
255
99,9
·
· ·
MESSAGES
(211ºF)
L5
Access code (Password) request
·
· ·
1
dEF
Indicates a defrost is underway. (Only if parameter d2=2)
·
· ·
Probe 1 faulty (open circuit, crossover, NTC: temp. >99°C or <-50 °C
255
E1
PTC: temp. >150 °C or <50 °C) - (equivalent limits in °F)
· ·
1
Probe 2 faulty (open circuit, crossover, NTC: temp. >99°C or <-50 °C
E2
PTC: temp. >150 °C or <50 °C) - (equivalent limits in °F)
·
· ·
1
AH
Flashing: maximum temperature alarm on probe 1 (A1)
·
· ·
255
AL
Flashing: minimum temperature alarm on probe 1 (A2)
·
·
·
AE
External alarm activated (only if parameter P10 or P11=2)
AES
Severe external alarm activated (only if parameter P10 or P11=3)
Adt
Defrost time-out alarm (only if parameter A8=1)
Door open alarm (Only if P10 or P11=1 and as per time at A12)
PAb
99,9
· ·
(211ºF)
D: Displays the message on the display, A: Activates the alarm relay (if available).
· ·
20,0
· ·
1
· ·
1
7- Technical specifications
· ·
99
AKO-D14112. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Power supply
· ·
1
AKO-D14123-2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 230 V~ ±10% 50/60 Hz 3.5 VA
AKO-D14220/D14320/D14120-2 . . . . . . . . . . . 120 V~ +8% -12% 50/60 Hz 4 VA
· ·
AKO-D14223/D14323. . . . . . . . . . . . . . . . . . . . . . 230 V~ ±10% 50/60 Hz 3.75 VA
AKO-D14212/D14312 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
·
· ·
1
Maximum Voltage SELV circuits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 V
99,9
·
· ·
Inputs (According to P4) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 input NTC/PTC + 1 digitised input
(211ºF)
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 input NTC/PTC + 2 digitised input
150
·
· ·
-
(302ºF)
Relay COOL AKO-D14123-2 2 CV . . . . . . . . . . . . . . . . . . . . . . . . . (EN60730-1: 16(10) A 250 V~)
·
· ·
Other models 16 A . . . . . . . . . . . . . . . . . . . . . . . . . . . . (EN60730-1: 12(9) A 250 V~)
A1
Relay FAN 6 A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . (EN60730-1: 5(4) A 250 V~)
·
· ·
120
0
·
· ·
Relay AUX 8 A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . (EN60730-1: 8(4) A 250 V~)
99
·
· ·
99
Number of relay operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . EN60730-1: 100.000 operations
Types of probe . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . NTC AKO-149xx / PTC AKO-1558xx
·
· ·
120
Measurement range NTC. . . . . . . . . . . . . . . . . . . . . . . . . . . . . -50,0 ºC a +99,9 ºC (-58,0 ºF a 211 ºF)
·
· ·
120
Resolution . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0,1 ºC
·
· ·
1
Working environment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -10 a 50 ºC, humidity <90 %
·
·
1
Ambient storage humidity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -30 a 70 ºC, humidity <90 %
Class of protection - front panell. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . IP65
·
· ·
20,0
·
· ·
Fixation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Panel-mounted with anchors
120
·
· ·
Panel cutout dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71 x 29 mm
Front panel dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79 x 38 mm
Depth . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61 mm
·
1
Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Screw terminals for cables up to 2.5 mm²
·
· ·
255
Rating of control device: built-in, automatic operation feature Type 1.B, for use in clean environments,
·
· ·
2
Class A software and continuous operation. Pollution classification 2 s/ UNE-EN 60730-1.
Double insulation between supply, secondary circuit and relay output.
·
· ·
2
Rated pulse voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2500 V
·
· ·
Temperature during ball-pressure test
255
· ·
1
3
Voltage and current as per EMC tests
·
· ·
3
·
· ·
2
Current of radio jamming supression tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 270 m
·
· ·
1
1=Door contact
2=External alarm
5=Act. ECO mode by pushbutton
7= Not used
8=Remote defrost
1=Door contact
2=External alarm
5=Act. ECO mode by pushbutton
7= Not used
8=Remote defrost
Control Acceso e Información
Description
Descripción
4
5
2
3
Frozen
Fruits and
Fresh
Soft Drinks
vegetables
fish
-18 (-0,4ºF)
10 (50ºF)
0 (32ºF)
3 (37,4ºF)
4
4
4
24
20
20
20
20
0 (32ºF)
30 (86ºF)
8 (46ºF)
8 (46ºF)
0
1
1
1
0
0
0
0
PTC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -50,0 ºC a +150 ºC (-58,0 ºF a 302 ºF)
Accessible parts. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75 ºC
Parts which position active elements . . . . . . . . . . . . . . 125 ºC
AKO-D14123-2/D14223/D14323 . . . . . . . . . . 207 V, 17 mA
AKO-D14220/D14320/D14120-2 . . . . . . . . . . 105 V, 36 mA
AKO-D14112/D14212/D14312 . . . . . . . . . . . 9,6 V, 181 mA
·
·
·
0
0
9
·
·
·
0
0
9
·
· ·
0
0
1
·
· ·
0
0
1
·
·
0
0
1
·
· ·
Valores Mín. Def. Máx.
Min. Def. Max.
Values
·
· ·
0
-
99
-
·
· ·
-
·
· ·
·
· ·
·
· ·
7
6
8
Bottle Racks
AC
Heat/
Incubators
12 (53,6ºF)
21 (69,8ºF)
37 (98,6ºF)
-
24
96
20
0
-
-
30 (86ºF)
99 (210ºF)
1
1
-
0
0
1
D
D
D
A
D
A
D
A
D
A
D
A
D
A
D
D
_
~
12/24 V
±20% 2.5 VA
_
12 V ~
±20% 2 VA
A