AKO AKO-14712 Instrukcja obsługi
Przeglądaj online lub pobierz pdf Instrukcja obsługi dla Termostat AKO AKO-14712. AKO AKO-14712 2 stron. Digital thermostats up to 150c for 1 ptc probe and 1 spdt relay
1471H200
HOJA TÉCNICA
Termostatos digitales hasta 150ºC
E
con 1 sonda PTC y 1 relé SPDT:
AKO-14712, AKO-14716
DESCRIPCIÓN GENERAL:
Termostatos electrónicos panelables, adecuados para visualizar, controlar y regular generadores de frío o de calor.
VERSIONES:
MODELO
ANCLAJE
AKO-14712
Panelable
AKO-14716
Panelable
DATOS TÉCNICOS:
Rango de temperatura: ........................................................................................................................................-50ºC a 150ºC
Entrada sonda PTC: ........................................................................................................................................Ref. AKO-1558X
Precisión del controlador: ....................................................................................................................................................±1ºC
Tolerancia de la sonda a 25ºC: ......................................................................................................................................±1.25ºC
Temp. ambiente de trabajo: ......................................................................................................................................5ºC a 50ºC
Temp. ambiente de almacenaje: ............................................................................................................................-30ºC a 70ºC
-de montaje independiente
-de característica de funcionamiento automático Acción Tipo 1.B
Clasificación dispositivo de control:
-para utilización en situación limpia
-soporte lógico (software) clase A
INSTALACIÓN:
Termostato:
El termostato debe ser instalado en un sitio protegido de las vibraciones, del agua y de los gases corrosivos, y donde la
temperatura ambiente no supere los valores reflejados en los datos técnicos.
Para que el equipo tenga un grado de protección IP65 deberá instalarse correctamente la junta entre el aparato y el perí-
metro del hueco del panel donde deba montarse.
Sonda:
Para que la lectura sea correcta, la sonda se ha de instalar en un sitio sin influencias térmicas ajenas a la temperatura que
se desea medir o controlar.
Conexionado:
Ver esquema en la etiqueta de características de los aparatos.
Los cables para el conexionado de los contactos de los relés deberan tener una
sección de entre 1 mm
2
y 2,5 mm
2
.
La sonda y su cable correspondiente NUNCA deben instalarse en una con-
ducción junto con cables de potencia, control o alimentación.
El circuito de alimentación debe estar provisto de un interruptor para su des-
conexión de mínimo 2A, 230V, situado cerca del aparato. Los cables entrarán
por la parte posterior y serán del tipo H05VV-F 2x0.5 mm
Anclaje:
Para la fijación del aparato situar los anclajes 1 sobre las guias 2 en la posición
de la figura. Desplazar el anclaje en el sentido de la flecha. Presionando la pes-
taña 3 puede desplazarse el anclaje en sentido contrario a la flecha.
FUNCIONES DEL FRONTAL
Funciones:
En programación, sube el valor que se está visualizando.
Pulsando durante 5 segundos se visualiza la temperatura del PUNTO
DE AJUSTE (Set Point).
En programación, baja el valor que se está visualizando.
Pulsanso simultáneamente durante 10 segundos se entra en el menú
+
de programación.
+
Pulsando simultáneamente se fija el nuevo valor.
LEDS indicadores:
LED PR permanente: Fase de programación de parámetros.
LED PR intermitente: Fase de programación del PUNTO DE AJUSTE (Set Point).
LED 1 permanente:
Relé activado (ON).
LED 1 intermitente:
Por temperatura detectada en la sonda debería estar
activado el relé, pero no lo está debido algún parámetro
programado.
AJUSTE DE LA TEMPERATURA:
El valor de fábrica, de AJUSTE DE TEMPERATURA (Set Point) por defecto es
de 0°C.
- Pulse la tecla
durante 5 segundos. Se visualizará el valor del AJUSTE (Set
Point) actual y se iluminará el LED PR de forma intermitente.
- Pulse las teclas
ó
para seleccionar el AJUSTE (Set Point) al valor dese-
ado.
- Pulse las teclas
+
simultáneamente para fijar el nuevo valor. Al realizar
esta operación, el display volverá a la situación de indicación de temperatu-
ra y el LED PR dejará de iluminarse de forma intermitente.
NOTA: Si no se pulsa tecla alguna durante 30 segundos en cualquiera de los
pasos anteriores, el controlador volverá automáticamente a la situación de
indicación de temperatura, sin modificar el valor del AJUSTE (Set Point).
Edición 03
RELÉ
ALIMENTACIÓN, 50/60 Hz
8A,cos
=1(SPDT)
12 V
, ±20% 96 mA
8A,cos
=1(SPDT)
230 V
, ±10% 7.8 mA
máx.
18 mm
2
o H05V-K 1x0.5mm
2
.
61,5
LED 1 1
2
5 seg.
5 Sec
INDICACIÓN
TEMPERATURA
CURRENT
TEMPERATURE
FRÍO
COLD
Diferencial
Differential
RELÉ OFF
RELAY OFF
-T
PUNTO DE AJUSTE
SET POINT
Digital thermostats up to 150°C
GB
for 1 PTC probe and 1 SPDT relay:
AKO-14712, AKO-14716
GENERAL DESCRIPTION:
Electronic thermostats (for panel and for surface), suitable for displaying, controlling and adjusting cold or heat generators..
VERSIONS:
MODEL
AKO-14712
AKO-14716
TECHNICAL DATA:
Temperature range: ..............................................................................................................................................-50ºC to 150ºC
PTC probe input: ..............................................................................................................................................Ref. AKO-1558X
Controller accuracy: ..............................................................................................................................................................±1ºC
Probe tolerance at 25 °C: ................................................................................................................................................±1.25ºC
Working ambient temperature: ..................................................................................................................................5ºC to 50ºC
Storage ambient temperature:................................................................................................................................-30ºC to 70ºC
Control device classification:
INSTALLATION:
Thermostat:
The thermostat must be installed in a place protected from vibrations, water and corrosive gases, and where the ambient
temperature does not surpass the values specified in the technical data.
For the equipment for panel to be suitable having IP65 protection the gasket should be installed properly between the appa-
ratus and the perimeter of the panel cut-out where it is to be fitted.
Probe:
To give a correct reading, the probe has to be installed in a place without heat influences other than the temperature that is
to be measured or controlled.
Connection:
See diagram in the unit rating plate.
3
2
Section of connecting wires for relays contacts must be between 1 mm
1
HUECO PANEL
PANEL CUT-OUT
70,5
FRONT PANEL FUNCTIONS:
LED PR
TECLA SUBIR
UP KEY
PR
TECLA BAJAR
DOWN KEY
Indicator LEDS:
LED PR constant: Parameters programming phase.
LED PR flashing : SET POINT programming phase.
LED 1 constant : Shows relay is ON.
LED 1 flashing : Means relay should be ON according to the temperature detected by the probe, but is not, owing to a
programming condition.
TEMPERATURE ADJUSTMENT:
.
AJUSTE
NUEVO
AJUSTE
ACTUAL
CURRENT
NEW
SET POINT
SET POINT
CALOR
HEAT
Diferencial
Differential
RELÉ ON
RELÉ ON
RELAY ON
RELAY ON
PUNTO DE AJUSTE
SET POINT
( 01 de 02 )
www.ako.es
FASTENING
RELAY
For panel
8A,cos
=1(SPDT)
For panel
8A,cos
=1(SPDT)
- with independent mounting
- with characteristic of automatic operation action, Type 1.B
- to be used in clean situation
-logical medium (software) class A
2
and 2,5 mm
The probe and its lead should NEVER be installed in a conduct next to power,
control or power supply wiring systems.
The power supply circuit should be connected with a switch for disconnection of
minimum 2A, 230V, located near the unit. The connection cables should be
H05VV-F 2x0,5mm
2
or H05V-K 1x0,5mm
Fastening of models for panel:
To fix the unit, place the fasteners 1 via the sliders 2 as shown in the figure. Move
the fasteners in the direction of the arrow. Press tab 3 to move the fasteners in the
opposite direction of the arrow.
Functions:
In programming, it increases the displayed value.
Press for 5 seconds to displays the Set Point temperature.
In programming it reduces the displayed value.
Held down simultaneously for 10 seconds brings up the programming
+
menu.
+
Held down simultaneously enters the new value.
The factory SET POINT value for temperature is 0ºC.
-Press the
key for 5 seconds. The current SET POINT value will be displayed
and LED PR will flash.
-Press the
or
keys to adjust the SET POINT to the required value.
-Press the
+
keys simultaneously to set the new value. The display will
revert to temperature indication status and the LED PR stop flashing.
NOTE: If no key is pressed for 30 seconds in either of the previous steps the con-
troller will automatically revert to the temperature indication status without
modifying the SET POINT value.
RELÉ OFF
RELAY OFF
+T
POWER SUPPLY, 50/60 Hz
12 V
, ±20% 96 mA
230 V , ±10% 7.8 mA
2
.
2
type, to posterior part of the unit.