Cylon CBX-8R8-H Arkusz danych technicznych i instrukcja instalacji - Strona 14

Przeglądaj online lub pobierz pdf Arkusz danych technicznych i instrukcja instalacji dla Kontroler Cylon CBX-8R8-H. Cylon CBX-8R8-H 15 stron.

Cylon CBX-8R8-H Arkusz danych technicznych i instrukcja instalacji

Output Override

HOA variants (CBX-8R8-H, FLX-4R4-H and FLX-8R8-H) include hardware override
switches for each of their outputs. The override controls are located behind the
flap on the front of the device:
CBX-8R8-H
And consist of a switch and a rotary knob for each output:
The channel number corresponding to the switch is shown directly below the switch.
The switch can be set to one of 3 positions:
When a switch is set to the Centre position the
corresponding output channel is set to Auto mode – the
output is controlled by strategy.
The rotary knob has no effect in this mode.
When a switch is set to the Bottom position the
corresponding output is forced to Off – both the strategy
setting and the rotary knob have no effect.
When a switch is set to the Top position the corresponding
output is set to Manual mode
for digital outputs, the output is forced on
for analog outputs the rotary knob setting controls the
output value.
Note: Manual position is supervised, i.e. the strategy is
aware of the manual value.
The Controller Strategy can determine if an override is in place is by connecting to
the
point on the output module:
Override
The value of the
point will be '0' when the output is active and '1' when
Override
the point has been manually overridden. This allows the strategy to react to the
fact that a point has been overridden.
Note: The corresponding terminal LED will indicate the override condition.
DS0119 rev 40
©2018 Cylon
FLX-4R4-H
FLX-8R8-H
All Rights Reserved.
Subject to change without notice
WWW.CYLON.COM
page 14 of 14