INSTALLATION, OPERATING AND MAINTENANCE INSTRUCTIONS
The following is intended to provide the basic instructions for installation, operating and maintenance of the Omega SDTM Monitor.
Read and understand these operating instructions before use.
PRODUCT RATINGS:
Maximum Flow:
Maximum Pressure:
PRODUCT WARNINGS:
The reaction force when flowing at the maximum pressure and flow listed above is 900 pounds. The center of the waterway
is 8
3
/
inches from the bottom of the inlet flange. Ensure these values plus an appropriate safety factor are used to
4
determine a proper support structure.
WARNING:
INSUFFICIENT STRUCTURAL SUPPORT CAN LEAD TO FAILURE, WHICH HAS POTENTIAL TO CAUSE AN INJURY.
THEREFORE, ADDITIONAL STRUCTURAL SUPPORT AT THE INLET MAY BE REQUIRED. NO SUPPORT
STRUCTURE IS TO BE ADDED DIRECTLY TO THE MONITOR. (Contact Akron Brass Customer Service
for assistance.)
WARNING:
Charge the unit slowly. Rapid charging may cause a pressure surge which has the potential to cause an injury or
damage the monitor.
WARNING:
Aim the unit in a safe direction before pumping water through it.
WARNING:
DO NOT exceed the maximum pressure or flow ratings of the monitor. Exceeding these ratings has the potential
to cause an injury or damage the monitor.
WARNING:
DO NOT install shutoffs on the outlet of the monitor. Shutoffs increase the potential for pressure surges due to
water hammer, which have the potential to cause injury or damage the monitor.
WARNING:
Drain the monitor after use to prevent "freeze damage".
WARNING:
Ensure the thread on the nozzle swivel matches the thread on the monitor outlet. Do not over tighten the nozzle
onto the unit.
MONITOR ATTACHMENT:
The monitor is to be mounted on the waterway with eight
mounting to a four inch flange. When mounting to a three inch flange, only four bolts, nuts and washers are required.
OMEGA SD™ MONITOR, STYLE 3524
1250 gpm (4800 lpm)
200 psi (1400 kpa)
5
/
inch bolts and nuts of grade five minimum and suitable washers when
8
120591