4. Comparator-Switch / Loop Check Mode: Access by pressing MODE for less
than 3 seconds.
A.
Comparator-Switch Setting: To activate / deactivate comparator-switch,
scroll to US1 (4-20mA version only) or US2 and select USE / noU. Enter com-
parator-switch set point by selecting A-1 or A-2 and use #/$ keys for pres-
sure setting. Now enter 'deadband' value (pressure difference between set
and reset values) by selecting b-1 or b-2 and use #/$ keys for setting. Note:
unit automatically configures the reset point. Increasing setpoint is entered as
a positive 'deadband' value, while decreasing setpoint is entered as a negative
'deadband' value.
B.
Loop Check: Allows the user to check comparator-switch operation without
requiring pressure input. Use $ or # keys to view comparator-switch function
in a simulated test of the application.
Comparator-Switch Setting / Loop Check Menu
Measurement Mode
MODE
Press 3 sec.
MODE
or longer
Press 3 sec.
or longer
Function Setting Mode
Select Comparator Mode
MODE
Comparator Operation
Selection
MODE
Filter Setting
MODE
Power-save setting
MODE
LED Ring Feature Setting
MODE
Display Unit Setting
Display Scaling
MODE
Decimal Point Position
(Display Scaling)
Set Offset Value
(Display Scaling Set)
Full Scale Value
Only in Output Selection
MODE
Pressure when the
analog is at zero point
Pressure when the
analog is at span point
After 1 second
(n ~ P
kY5
Message displayed
Current setting
After 1 second
OP(
npn
Message displayed
Current unit
setpoint
After 1 second
f;l
f-1
Message displayed
Current setting
Time constant 2.5s
After 1 second
e(O
e(O
eOf
Message Display
Current Setting
After 1 second
lRg
L
lRI
Message Display
Current Setting
Comparator 1 & 2 are
interlocked with LED
After 1 second
UN;
u
P5I
Message Display
Current Setting
After 1 second
d-p
d
Message Display
Current Setting
MODE
After 1 second
d-l
d
Message Display
Current Setting
MODE
After 1 second
d-K
d
Message Display
Current Setting
ANALOG OUPUT SCALING
After 1 second
A-L
a
Message Display
Current Setting
MODE
After 1 second
a-k
a
100. 0
Message Display
Current Setting
4
Select with
X W
keys
kY5
!;n
Hysteresis
Window comparator
Select with
X W
keys
npn
pnp
NPN output
PNP output
X W
Select with
keys
f-0
f-1
f-2
Filter off
Time constant 25ms
Time constant 250ms
f-4
f-5
f-3
Time constant 5s
Time constant 10s
Select with
X W
keys
EoF
Eon
Power-save OFF
Power-save ON
Select with
X W
keys
Lr0
Lr1
No LED interlock
Comparator 1 is
interlocked with LED
Lr3
Lr2
Comparator 2 is
interlocked with LED
Select with
X W
keys
ET[
P5I
psi, bar or mPa
Display Scaling
DISPLAY SETTING
X W
Select with
keys
0
0. 0 0
0. 0 00
0. 0 0
0. 0 0
X W
Key to Select Between
(–)1999~(+)9999
X W
0. 0 0
Key to Select Between
(–)1999~(+)9999
Set Any Desired Position Within the
0. 0
X W
–100 to 150% range with the
Set Any Desired Position Within the
X W
–100 to 150% range with the
0. 0
keys
keys