ASHE STL-96 Instrukcja obsługi - Strona 8
Przeglądaj online lub pobierz pdf Instrukcja obsługi dla Sprzęt nagrywający ASHE STL-96. ASHE STL-96 17 stron. Stream selector six channel
Press theSHIFT key to move the cursor to the last digit.
Enter the Password 0004 by using INC key and then press MODE key. After pressing MODE key the
OLED Display will show as follows :-
Feed 4mA DC Current from a reliable 4 to 20mA source to the instrument. The display will show the
corresponding ADC Count corresponding to 4mA input current.
Press theAUTO/MANUAL key to save the ZERO calibration point of 4-20mA DC Input.
The OLED Display will show the message DATA SAVED to acknowledge this setting.
Press MODE key to move on to the Span Calibration point.After pressing theMODE key, the OLED
Display will show:
Feed 20mA DC Current from 4 to 20mA source to the instrument. The display will show the
corresponding ADC count corresponding to 20 mA DC input current.
Press theAUTO/MANUAL key to save the SPAN calibration point of 4-20mA DC Input.The OLED Display
will show the message "DATA SAVED" to acknowledge this setting.
This will complete the input signal 4-20mA DC calibration of the instrument.Press theMODE key to exit
from Input Calibration Mode.
After pressing theMODE key, the OLED Display will return to PROCESS SCREEN.
INPUT RANGE MODE: -
The ASHE Stream Selector Model STL-96has the facility to change the resolution and range of the
displayed process value.
Enter 4-ma
00123
DATA SAVED
Enter 20-ma
00123
DATA SAVED