Valve Actuator moves at the end
Loose screws
of the open or closed function.
No Power to the
Bad wiring
Controller
Open breaker or blown fuse
Power not connected.
Valve Actuator does not work.
1. No signal from the Controller
Motor does not drive.
to the Actuator Motor.
2. Defective Actuator Motor
3. Worm Gear system jammed.
4. Planet Gear system jammed.
Motor Runs but Valve does not
1. Grove Pin is missing from the
operate
Shaft.
2. Gear Sector is not engaging
the Worm Gear.
3. Motor Shaft is disengaged
from the Planet gears.
Valve closes when the OPEN
1. Sector Gear is in the wrong
Button is pressed and vice versa.
position.
2. Cable wiring is reversed.
Valve OPEN/CLOSE LED's switch
1. Wiring
immediately from Red to Green
2. Mechanical Binding
and vice versa.
APPENDIX
Mating Weather-Pack Connectors for Power Cable
A Mating Weather-Pack connector must be used to connect to the power source.
DO NOT CUT THE CONNECTOR on the power wire of the controller.
Doing so will void the warranty.
Part number 9300-0058 is a packet of (5) mating Weather-Pack connections.
Wiring Harnesses
Part Number
Description
7-21-290
10' long (standard length)
7-21-381
15' long
9303-0016
20' long
9303-0012
30' long (utilizes Potting Shells and 10 gauge wire)
9303-0013
38' long (utilizes Potting Shells and 10 gauge wire)
9303-0014
50' long (utilizes Potting Shells and 8 gauge wire)
Auxiliary Cables
Part Number
Description
9300-0052
10' long (standard length)
9300-0055
25' long
9300-0056
50' long
PHONE: 330.264.5678 or 800.228.1161 I FAX: 330.264.2944 or 800.531.7335 I www.akronbrass.com
WARRANTY AND DISCLAIMER: We warrant Akron Brass products for a period of five (5) years after purchase against defects in materials or workmanship. Akron Brass will repair or replace
product which fails to satisfy this warranty. Repair or replacement shall be at the discretion of Akron Brass. Products must be promptly returned to Akron Brass for warranty service.
We will not be responsible for: wear and tear; any improper installation, use, maintenance or storage; negligence of the owner or user; repair or modification after delivery; damage; failure to
follow our instructions or recommendations; or anything else beyond our control. WE MAKE NO WARRANTIES, EXPRESS OR IMPLIED, OTHER THAN THOSE INCLUDED IN THIS WARRANTY
STATEMENT, AND WE DISCLAIM ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR ANY PARTICULAR PURPOSE. Further, we will not be responsible for any consequential,
incidental or indirect damages (including, but not limited to, any loss of profits) from any cause whatsoever. No person has authority to change this warranty.
ISO 9001 REGISTERED COMPANY
© Premier Farnell Corporation. 2012 All rights reserved. No portion of this can be
reproduced without the express written consent of Premier Farnell Corporation.
While some motion is normal from torque, excessive movement
may be caused by loosened screws.
Before tightening the screws, remove them and apply Permabond
LM 113 or Loctite 222 and retighten.
Check all power connections, wires, fuses or breakers.
Be sure a separate power wire is connected to any Controller used
as an Auxiliary.
1. Check all connectors are fully engaged.
Check the voltage through the Wiring Harness
should be at least 11.5 volts for 12 volt systems and
22 volts for 24 volt systems. Check the signal from
the Controller.
2. Remove the Motor from the Actuator and operate
the Motor to be sure the Motor Shaft turns freely.
3. Check the Worm Gear. Operate the Valve using the
Manual Override.
4. Remove the Motor and check the Planet Gears.
1. Check the Groove Pin is fully engaging the Worm
Gear and Shaft.
2. Check if the Worm Gear and Sector Gear are
engaged.
3. Remove the Motor and check for engagement of the
Motor Shaft and Planet Gears.
1. Reposition the Sector Gear.
2. Replace the Cable.
1. Check wiring as explained in Problem #1.
2. Remove the Motor and check the Shaft turns freely. Also, oper-
ate the Valve manually via the Override to check for binding.
Style 9313 Controller Ordering Information
Part Number
Description
9313-0001
Controller Only
9313-0002
Controller w/ 10' Wiring Harness
9313-0003
Controller w/ 10' Auxiliary Cable
REVISED: 4/12
STYLE 9313 CONTROLLER
INSTALLATION & OPERATING INSTRUCTIONS
The Style 9313 Controller from Akron is designed to provide reliable and accurate valve control with valve position
indication through 10 LED (Light Emitting Diodes) indicators identifying the degree of Open/Close.
Features of the Akron Style 9313 Controller include:
Protected against EMI (Electro Magnetic Interference), both incoming and outgoing
Programmable Auto Open (not preset)
Works with both 12 and 24 Volt systems
Retrofits to existing apparatus
4 ¼" square face
Meets all aspects of NFPA 1901
Carries Akron's 5 year warranty against manufacturing defects
Standard Components
Controller
Wiring Harness for connection to the valve-10' length standard
Note: the Controller is designed for use only with Akron Brass Electric Valves. Do not use with any other manufacture of valve. Doing
so will void any warranty.
INSTALLATION INSTRUCTIONS
Select the mounting location for the Controller. The Controller can be mounted from the outside with (4) Screws and
Delrin Nuts (included). Torque requirement is 6-8 lb-in for the nuts. The unit requires 2 ½" clearance behind the panel. Dimensions
for a panel cutout are shown in figure #1.
Warning: The Controller is a sealed unit. Disassembly of the unit will void any warranty. There are no user serviceable parts in the
Controller. If service is required the unit should be returned to the factory. Also, do not cut any connections. Doing so will void any
warranty and prevent product returns.
Note: The Valve and Auxiliary wires are plugged prior to shipment. These plugs must be removed before connections can be made. If
a lead is not being utilized, the plug should be left in place to prevent moisture damage.
CONTROLLER LEADS
Each Controller has three (3) Connectors extending from the back of the unit.
Power Connection lead
The Controller Power connection utilizes a 2 prong Weather-Pack connector. A mating Weather-Pack connector is required (cus-
tomer supplied-see appendix for purchasing information). Proper wire gauge is required to assure a quality connection. 12 gauge wire
is recommended. Heavier gauge wire is required for runs over 10'.
Note: when using larger than 12 gauge wire, be sure to use a 12 gauge connector and splice after the connector so as to not void any
warranty. The splice should be made close to the Controller.