MOUNTING HEATERS USING WALL BRACKET SET
A set of wall brackets is supplied with each heater. These brackets allow mounting angles between 30° and 45° to
the horizontal, and heaters must not be installed, on walls, at angles outside this range.
1.
Place brackets in proposed heater position on the wall. Check that they are properly aligned and mark in
hole positions for fixing screws (See Table below). Drill holes, fit plugs and use screws to fix brackets in
position.
2.
Fix each bottom side of the heater to the bottom side of its respective wall bracket, using the nuts and
bolts that are provided. Connect top sides of heater to bracket using the S-hooks and chain.
OTHER MOUNTING METHODS
Heaters may be suspended from roof structures by other methods. The drawing below illustrates the more commonly
used methods for mounting the heaters. Some local codes or application conditions, such as draughts that could
cause units to swing, stipulate that if flexible gas connectors are used then the heaters must be rigidly mounted.
THE HEATER FACE MUST NOT MAKE AN ANGLE OF LESS THAN 15 ° ° ° ° ° WITH HORIZONTAL.
The flue outlet area of the heater must remain free of obstructions at all times. Gas pipework or electrical cables
must never be used to lend mechanical support to the heater.
M ODEL
DIMENSION
A
DR 30
125
RV 45
287
DR 50
287
DR 60
287
DR 80
453
138
DR 90
453
DR 100
453
DR 120
615
DR 130
615
DR 150
695
DR 160
695