AMCI DC60 Manual do utilizador - Página 10
Procurar online ou descarregar pdf Manual do utilizador para Conversor de multimédia AMCI DC60. AMCI DC60 20 páginas. Multi-turn analog output duracoder
DC60 S
PECIFICATIONS
Output Load Calculations
Voltage Output DuraCoder
A voltage output DuraCoder can drive an output load of 2 k or greater. If the output load is greater that
10 k, consider installing a 10 k resistor in parallel with the input terminals for greater noise immunity.
Current Output DuraCoder
The maximum load that can be driven by a current output DuraCoder depends on the power supply voltage
applied to the +DC Power Input (Pin 1). For input voltages up to 15 Vdc, the maximum load is 475 . For
input voltages greater than or equal to 15 Vdc, the formula for determining the maximum load is given below
along with a simple graph of the curve.
R
LOAD
MAX
10
(+DC Input Voltage) – 2.5Vdc
=
Figure 5 Maximum Load Resistance - Current Output
Maximum Load Resistance (ohms)
ADVANCED MICRO CONTROLS INC.
Analog DC60 User Manual