Transporting and Unpacking the Tank
Most FLOFAB® Tanks are not crated at the factory. Larger tanks are shipped with lifting lugs attached
to provide a safe means for lifting and moving the unit.
▼ The tank should only be lifted by the lifting lugs provided. Improper lifting of the tank may result
in damage to the unit.
▼ Care should be taken not to «drop» or damage the tank during transport and unpacking. This
could result in damage to the hydraulic cement lining of the tank.

Location Requirements

FLOFAB® Tanks are designed for indoor use only, and require at least two feet (2') of clearance
around and above the unit, unless otherwise required by the design specifications. The tank should
be located on a level surface (no more than one-half degree [½º] of slope), capable of supporting
the total weight of the tank when filled to capacity.
Examining the Tank
After the tank has been set in place and uncrated (if necessary), it should be carefully examined to
assure that it was not damaged during shipping. If any evidence of damage is detected that could
affect the tank, contact FLOFAB, or your authorized sales representative, to report the damage and
to receive instructions on how to proceed.
Mounting the Tank
The tank should be mounted to the floor, following applicable architectural / local code requirements,
or accepted standards for the specific installation site and for the tank purchased.
In areas prone to seismic activity, it is recommended that the tank be mounted to the floor, according