American Rotary AUL 208-240V Manual do utilizador - Página 10
Procurar online ou descarregar pdf Manual do utilizador para Transformador American Rotary AUL 208-240V. American Rotary AUL 208-240V 18 páginas.
5.0 OPERATION + MAINTENANCE
5.1 STARTING + STOPPING
American Rotary phase converters are started and stopped with a mechanical push button . As with most
electrical equipment, frequent stops and starts are harder on the rotary phase converter than steady operation .
The rotary phase converter is extremely low cost to operate at idle (with no three-phase load), and this is
preferable to a high level of stopping and starting . If your load situation dictates that the rotary phase converter
must be started and stopped frequently, call us about our Phase Monitor and Timer Kit for optimum product
operation .
5.2 CHECKING VOLTAGES
Measuring voltage is the easiest way to test to see if the phase converter is working properly . To get the most
accurate measurement, the three-phase load should be running when you are checking the voltage .
VOLTAGE MEASUREMENTS:
Measure L1/T1 to L2/T2
Measure L1/T1 to T3
Measure L2/T2 to T3
Do not measure line to ground . Voltages will vary widely when doing this .
5.3 GENERAL MAINTENANCE
The rotary phase converter may operate continuously with or without a load . The converter will run cool and
quiet in the no load condition because the voltages are well balanced .
1 . Never start the converter with a load applied (including transformers) .
2 . The converter should start within a second or two . Wait to start loads (including transformers) until the
converter reaches full speed . A timer circuit can be used to automatically start loads after the converter
reaches full speed .
5.3.1 MAINTENANCE
Keep dust and moisture away from the unit . Keep dust from accumulating in the motor and on the air vents on
the side of the unit . Dust can be blown out using compressed air .
Annually check the wires and connections on the phase converter . No connections or wires should be loose .
Also inspect for damaged or missing insulation . Be sure that power is disconnected when doing so!
10 | User Manual R2 .3
This is your single-phase voltage as supplied from the utility . To get the most
accurate voltage measurement, make sure that the converter is on and the load is
applied .
This is the voltage between the manufactured line (T3) and one of the single
phase lines . This voltage should be up to 5% higher than the T1 to T2 single-phase
voltage .
This voltage is the least important . It should also be within 5% . This voltage will
drop down into spec . when a load is applied .