A flash of the LED loads indicates that the first menu has
been accessed: "MENU 1". The access to each menu is
sequential.
Menu 1: minimum dimming value setting
Each single click allows you to vary between 7 minimum
dimming values. The following minimum levels are availa-
ble: 0.1%, 1%, 5%, 10%, 20%, 30% and 100%.
Once the minimum dimming value has been selected,
then long press to confirm: a double flash confirms the
passage to MENU 2.
i
Note. Only in case the minimum level is set to
100%, once the setting is confirmed, the device au-
tomatically exits the MENU.
Menu 2: power-on ramp (fade in) setting
Each single click allows to set the fade in. The following
"fade in" times are available: instantaneous, 1 second, 2
seconds, 3 seconds, 6 seconds.
Once the "fade in" time has been selected, then press
and hold to confirm: three flashes confirm the passage
to MENU 3.
Menu 3: power-off ramp (fade out) setting
Each single click allows to set the fade out. The following
"fade out" times are available: instantaneous, 1 second, 2
seconds, 3 seconds, 6 seconds.
After selecting the "fade out" time, then long press to con-
firm: three quick flashes confirm the storage of the set-
tings and the exit from the menu.
Once exited the menu, the LED load connected to the
dimmer output turns on at the minimum value set.
Functions
Relationship between DALI bus and local commands:
on power-up, in case the bus connection is not present,
the local command is active. When the bus connection
is detected, the control passes to the bus. In the absen-
ce of the signal, if the local command is an N.O. button,
the control is passed to the local commands the button is
pressed.
Device addressing
• Simplified method (one ballast connected at a time):
each one will get the address progressively from 0 to
63;
• Random Address Allocation: by connecting all the bal-
lasts at the same time, each one will get a random
address.
Subsequently, the address configuration can be changed
by using an application for parameterization, for example
by downloading the ekinex CGEKBG1TP software to your
PC which allows to:
• configure the DALI system and define its parameters;
• set the DALI luminaires (groups, scenarios, IDs, etc.);
• test the communication on the DALI bus;
• update the device.
The software can be downloaded from www.ekinex.com
website and its use is described in the application manual
of the ekinex EK-BG1-TP DALI Gateway. The software
requires Microsoft Windows (7 and later).
DALI address map
The intensity and ON / OFF switching of the output is ma-
naged via the DALI channel.
Address
Dimensions[mm]
43.00
Marks
• CE: the device complies with the Electromagnetic
Compatibility Directive (2014/30/EU) and the RoHS 2
Directive (2011/65/UE).
• Reference
55015:2013+A1:2015,
50581:2012, IEC/EN 62386-101/102.
5
i
Note. In order to install and use the CGEKBG1TP
configuration software, it could be necessary the
installation of .NET Framework 4, which can bee
freely downloaded from Microsoft.com website.
Function
Map: dimmer
0
Dimmer
Dimmer (Intensity value) 0 .. 254
43.00
23
Standards:
EN
61347-1:2015,
EN
EN
61547:2009,
EN