DAB PUMPS ACTIVE DRIVER M/M 1.1 Instruções de instalação e manutenção - Página 8

Procurar online ou descarregar pdf Instruções de instalação e manutenção para Unidade de controlo DAB PUMPS ACTIVE DRIVER M/M 1.1. DAB PUMPS ACTIVE DRIVER M/M 1.1 16 páginas.

8.3
OPERATION : PARAMETERS FOR THE USER
Access keys MODE & SET for 2 seconds
8.3.1 SP : Setting the set point pressure ( in bar )
From normal operating status, hold down the MODE and SET keys simultaneously until the letters
SP appear on the display. In these conditions the + and – keys allow you respectively to increase and
decrease the desired pressure value.
The regulating range is from 1.0 to 6.0 bar for the A.D. M/M 1.1 and from 1.0 to 9.0 bar for the other models.
Press SET to return to normal operating status.
As well as the working pressure the ACTIVE DRIVER allows you to set two other values:
RP: expresses in bars the decrease in pressure, with respect to SP, that makes the pump restart.
DP: expresses in bars the desired decrease in pressure at low flow rates.
The three parameters are related to each other.
Diagram for regulating pressure according to in flow rate
SP
Example:
SP = 4.5 bar
DP = 1.0 bar
RP = 0.7 bar
During normal operation the system will be pressurised at 4.5 bar.
In case of low flow rates (losses) the system will be pressurised at 3.5 bar.
The electropump restarts when the pressure falls below 2.8 bar.
8.4
OPERATION : PARAMETERS FOR THE INSTALLER
Access keys MODE & SET & - for 5 seconds
If an error or malfunction occurs during this phase, the display is not changed. Depending on
the type of error, the electropump may switch off. However it is still possible to make the
desired calibration. To know the type of error that has occurred you must return to the mode
in which you see the operating status by pressing the SET key.
From normal operating status, hold down the MODE & SET & - keys simultaneously until the letters "rC"
appear on the display. In these conditions the + and – keys allow you respectively to increase and decrease
the value of the parameter while the MODE key allows you to move on to the next parameter in cyclic mode.
Press SET to return to normal operating status.
8.4.1
rC : Setting the rated current of the electropump (excluding A.D. M/M 1.1)
This parameter must be set the same as the current on the motor data plate (Amps) in the configuration
in which it is used (power supply 230V for A.D. M/T - power supply 400V for A.D. T/T).
8.4.2
rt : Setting the direction of rotation (excluding A.D. M/M 1.1)
Possible values: 0 and 1
If the direction of rotation of the electropump is not correct, it is possible to invert the direction of
rotation by changing this parameter.
If it is not possible to observe the direction of rotation of the motor, proceed as follows:
-
Open a user and observe the frequency (parameter Fr with MODE key from GO) and the current
(parameter C1).
-
Without changing the amount of water taken, change the parameter rt and observe the frequency Fr
and the current C1 again.
-
The correct parameter rt is the one which, with the same amount of water taken, requires a lower
frequency Fr and current C1.
ENGLISH
p
DP
RP
5 l/min
Pressure set in the system
Reduced pressure for low flow rates
Electropump restarting threshold
29
Q