The ACTIVE DRIVER is already provided with current protections. If a magnetothermal switch is
installed in line, it must have a max. capacity of 16A.
6.4
The connection of the line to the ACTIVE DRIVER must include the earth line. The total earth
resistance must not exceed 100 Ohm.
6.5
To protect the system it is recommended to install a differential switch with correct
dimensions, type:
Class A, with adjustable dispersion current, selective, protected against sudden
tripping.
The automatic differential switch must be marked with the following two symbols:
7.
HYDRAULIC CONNECTIONS
7.1
Always install a check valve on the pipe upstream from the ACTIVE DRIVER.
For the purposes of operation of the ACTIVE DRIVER it does not matter whether the valve is fitted
on the suction or on the delivery of the pump.
7.2
The hydraulic connection between the ACTIVE DRIVER and the electropump must not have any
derivations.The dimensions of the pipe must be suitable for the electropump installed.
7.3
The ACTIVE DRIVER works at constant pressure. This regulation is appreciated if the hydraulic
system downstream from the system is of suitable dimensions.
Systems made with pipes that have too narrow a section introduce load losses which the appliance
cannot compensate; the result is that the pressure is constant on the device but not on the user.
When electrical and hydraulic installation have been completed, supply power to the system and check the
direction of rotation of the electropump. If it is not correct, invert two phases on the motor terminal board.
8.
CHARACTERISTICS – INTERPRETATIONS – OPERATION
The ACTIVE DRIVER is an innovative integrated system for controlling electropumps with variable speed, able to
keep a constant pressure while the flow rate varies.
The ACTIVE DRIVER is composed of an inverter, a pressure sensor and a flow sensor.
With the exclusion of models M/M 1.1 and M/T 1.0 the ACTIVE DRIVER is provided with 3 inputs and 2 outputs so
as to be able to realise certain interface solutions with more complex installations.
Figure 1 shows the logical function diagram for the connection of the user input terminals.
Figure 2 shows the logical function diagram for the connection of the alarm output terminals.
Figure 3 shows the connection diagram for 2 ACTIVE DRIVER units, for the exchange function.
8.1
CHARACTERISTICS AND INTERPRETATIONS
Ref.
L – N
SINGLE-PHASE
R – S – T
THREE-PHASE
U - V- W
THREE-PHASE
R – S
SINGLE-PHASE
Power supply terminal: + 12V DC – 50Am.
J22 - 1
(excluding A.D. M/M 1.1 and A.D. M/T 1.0)
Connection terminal of input i3 for general disabling command.
J22 - 2
(excluding A.D. M/M 1.1 and A.D. M/T 1.0)
Connection terminal of input i2 for selecting set point 1.
J22 - 3
(excluding A.D. M/M 1.1 and A.D. M/T 1.0)
0V connection terminal (GND) for joining I
J22 - 4
(excluding A.D. M/M 1.1 and A.D. M/T 1.0)
Connection terminal of input i1 for protection against dry running.
J22 - 5
(excluding A.D. M/M 1.1 and A.D. M/T 1.0)
ENGLISH
Power supply line connection terminals.
Line earth system connection terminal.
Three-phase pump 230 V connection terminals
Pump earth system connection terminal.
FUNCTION
– I
to GND.
3
2
27