Akytec MV110-16DN Manual do utilizador - Página 5

Procurar online ou descarregar pdf Manual do utilizador para Unidade de controlo Akytec MV110-16DN. Akytec MV110-16DN 19 páginas. Analog input module, 16 channel

Akytec MV110-16DN Manual do utilizador

Specifications

2. Specifications
Table 2.1 General technical data
Power supply
Power consumption, max.
Inputs
Outputs
RS485 interface
Dimensions
Weight
Material
Table 2.2 Technical data of inputs
Input signal
Galvanical isolation
Pulse frequency, max.
Pulse length, min.
Integrated voltage source
Current, max.
Logical „1", min.
Logical „0", max.
Lead resistance, max.
2.1

Environmental conditions

The module is designed for natural convection cooling. It should be taken into account
when choosing the installation site.
The following environment conditions must be observed:
clean, dry and controlled environment, low dust level
closed non-hazardous areas, free of corrosive or flammable gases
Table 2.5 Environmental conditions
Ambient temperature
Transportation and storage
Relative humidity
IP code
Altitude
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany · Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de
Digital
Analog
Digital
Analog
Connection
Protocols
Baud rate
Data bits
Parity
Stop bits
Property
Condition
24 (20...28) V DC
Modbus RTU / ASCII, akYtec
2.4...115.2 kbit/s
even, odd, none
63 x 110 x 75 mm
approx. 240 g
MV110-16DN
Switch contact
NPN/PNP
1500 V, in groups of 4
1 kHz
0.5 ms
24±3 V
8.5 mA (with 27 V)
4.5 mA
1.5 mA
Permissible range
-20...+55°C
-25...+55°C
up to 80% (at +25°C, non-condensing)
IP20
up to 2000 m above sea level
6 W
16
̶
̶
̶
D+, D-
7, 8
1, 2
plastic
̶
4