Akytec TRM500 Manual do utilizador - Página 2
Procurar online ou descarregar pdf Manual do utilizador para Controlador Akytec TRM500. Akytec TRM500 2 páginas. Temperature controller
> 3 s
Operation
PROG
T
UP
T
NORM
T
DOWN
285.0
SET1
ON
REG
SET2
MAN
ALARM
Setpoint
SP1
adjustment
T
UP
T
NORM
T
DOWN
SP1
SET1
ON
REG
SET2
MAN
ALARM
PROG
T
UP
new
T
NORM
Setpoint
T
DOWN
SP1
SET1
ON
REG
SP1
SET2
MAN
ALARM
PROG
T
UP
T
NORM
T
DOWN
SP2
SET1
ON
REG
SET2
MAN
ALARM
T
new
UP
T
NORM
Setpoint
T
DOWN
SP2
SP2
SET1
ON
REG
PROG
SET2
MAN
ALARM
Appendix D. Digital input configuration (Parameter InP.F)
1. Setpoint switching
SP2
SP1
DI
InP.F = Set2
- switching SP1/SP2 or
InP.F = Add2
- switching SP1/SP2+SP2
2. Switching to Manual
SP1
DI
InP.F = mAn1 - switching to Manual, when switched back- control with the last setpoint
InP.F = mAn2 - switching to Manual, when switched back - control with the last measured
temperature instead of setpoint
3. Control on/off
SP1
DI
InP.F = r-S - control on/off
Password
17
PASS
T
UP
T
NORM
T
DOWN
Corr
SET1
ON
REG
SET2
MAN
ALARM
TRM500_0283_EN
© All rights reserved. Subject to technical changes and misprints.
Quick
Full
Exit
setup
setup
FuLL
oUt
FaST
PROG
PROG
Control
Cont
Sensor type [P100]
S.TYP
PROG
(see Table 2)
Lower alarm limit [0.0]
U.Lo
Range -250...+1800
Control [on.oF]
FUNC
Pid = PID
Upper alarm limit [100.0]
U.H
on.oF = ON/OFF
Range -250...+1800
Hysteresis [1.0]
Output mode [1.U]
CoNF
HYST
Range 0...1800
(see Appendix A)
1.U = OUT1 - ON/OFF or PID
OUT2 -
ON if T>U.Hi or T<U.Lo
Lower Alarm Limit [0.0]
OUT3 - OFF
U.Lo
1. = OUT1 - ON/OFF or PID
Range -250...+1800
OUT2 -
ON if U.Lo< T <U.Hi
OUT3 - OFF
2.U = OUT1 - OFF
Lower Alarm Limit [100.0]
OUT2 - ON if T>U.Hi or T<U.Lo
U.H
OUT3 - ON/OFF or PID
Range -250...+1800
2. = OUT1 - OFF
OUT2 - ON if U.Lo <T < U.Hi
OUT3 - ON/OFF or PID
o.ut
3.U = OUT1 - ON if T > U.Hi
OUT2 - ON if T < U.lo
OUT3 - ON/OFF or PID
Exit
PWM period [1.0]
PrD
Range 0...60 s
Minimum pulse length [0.050]
DL
Range 0...9.999 s
Control OUT1/OUT3 [on.oF]
FUNC
Pid = PID
on.oF = ON/OFF
Hysteresis [1.0]
HYST
Range 0...1800
P-component [10.00]
P D.P
Range 0.001...9999
I-component [50.0]
P D.
Range 0...999.9
D-component [25.0]
P D.D
Range 0...999.9
OUT
PROG
DI
Control signal
manipulation
DI
DI
Appendix E. Calibration
Flashing Y1
17
Y1
NULL
T
T
UP
UP
T
T
NORM
NORM
T
T
DOWN
DOWN
Corr
Corr
Corr
SET1
ON
REG
PROG
SET1
ON
REG
SET1
SET2
MAN
ALARM
SET2
MAN
ALARM
SET2
To calibrate the first point:
PROG
connect a resistance decade (for RTD) or mV-signal (for TC)
as a reference signal to the input „Sensor"
Measured value
5.3
5.0
T
UP
T
according to the
NORM
T
DOWN
Y1
reference signal
Y1
PROG
SET1
ON
REG
SET1
SET2
MAN
ALARM
SET2
MAN
flashing value
TRM500
Temperature controller
Appendix C. Configuration
Note: The values in the square brackets are factory settings
PROG
Sensor
SEnS
PROG
Sensor type [P100]
S.tYP
(see Table 2)
Offset [0.0]
Cor.A
Range -99.9...99.9
Filter time constant
F L.T
[0.01]
Range 0...30 s
Filter bandwidth[10]
F L.L
Range 0...100 °C
RTD circuit [3]
R.Con
2 = 2-wire
3 = 3-wire
4 = 4-wire
oUT
Exit
PROG
Exit
1a. Switching SP1/SP2
inP.F = Set2
2a. Manual control, indication
SP1 = 285
„Temperature/Control signal"
SP2 = 40
Measured value
284.9
TUP
TNORM
Measured value
TDOWN
SP1
285.0
SET1
ON
REG
SET2
MAN
ALARM
Setpoint
DI
284.9
Measured value
TUP
TNORM
Measured value
TDOWN
40.0
SP2
SET1
ON
REG
SET2
MAN
ALARM
Control signal
DI
Measured value
284.9
TUP
TNORM
Control signal
TDOWN
285.0
SP1
SET1
ON
REG
SET2
MAN
ALARM
Measured value
1b. Switching
inP.F = Add2
SP1/SP1+SP2
SP1 = 285
Measured value
SP2 = 40
Control signal
Measured value
284.9
TUP
TNORM
TDOWN
285.0
SP1
SET1
ON
REG
SET2
MAN
ALARM
Measured value
DI
Measured value
284.9
TUP
TNORM
TDOWN
325.0
SP1+SP2
SET1
ON
REG
SET2
MAN
ALARM
DI
284.9
Measured value
TUP
TNORM
TDOWN
285.0
SP1
SET1
ON
REG
SET2
MAN
ALARM
Calibration factor Y1=0
PROG
oUt
T
T
UP
UP
PROG
T
T
NORM
NORM
T
T
DOWN
DOWN
Corr
ON
REG
SET1
ON
REG
MAN
ALARM
SET2
MAN
ALARM
Adjust temperature
Y2
T
UP
T
UP
T
according to the
NORM
T
NORM
T
DOWN
T
reference table
DOWN
Corr
PROG
SET1
ON
REG
ON
REG
SET2
MAN
ALARM
ALARM
2nd point calibration
when required
Y3
T
UP
T
NORM
T
DOWN
Corr
SET1
ON
REG
SET2
MAN
ALARM
PROG
3nd point calibration
when required
APLY
T
UP
T
NORM
T
DOWN
Corr
SET1
ON
REG
SET2
MAN
ALARM
PROG
Digital input
Autotuning
D. nP
tuNE
PROG
PROG
Digital input mode [oFF]
NP.F
(see Appendix D)
oFF
= deactivated
r-S
= control ON/OFF
Set2
= switching SP1/SP2
Add2
= switching SP1/SP2+SP2
mAn1
= Manual
mAn2
= Manual, using the last
tunE
measured temperature
instead of SP1
PROG
Manual control -
P. n
Autotuning
Initial control signal [Last]
Range 0.00...100
Last = last value before switching
to Manual
tunE
Manual control -
P. nd
Indication [P]
P
= Control signal
t-P
= Temperature/Control signal
alternately
oUT
Exit
PROG
tunE
Switch to factory settings
Press
and
simultaneously, then
for confirmation
PROG
PROG
Disable cold junction compensation (CJC)
Press
and
simultaneously, then
for confirmation
PROG
PROG
inP.F = mAn1
2b. Manual control, indication „Control signal"
P.ini = 0.0
P.ind = t-P
284.9
TUP
T NORM
TDOWN
285.0
SET1
ON
REG
SET2
MAN
ALARM
DI
284.9
Control signal
TUP
T NORM
TDOWN
0.0
SET1
ON
REG
Measured
SET2
MAN
ALARM
Control signal
manipulation
Control signal
43.1
TUP
T NORM
TDOWN
Measured
284.9
SET1
ON
REG
SET2
MAN
ALARM
5 s
Measured
206.2
TUP
T NORM
TDOWN
43.1
SET1
ON
REG
SET2
MAN
ALARM
DI
206.2
if inP.F = mAn2 then
TUP
Setpoint = last mea-
T NORM
TDOWN
285.0
sured value
Setpoint
SET1
ON
REG
SET2
MAN
ALARM
save calibration factor Y1
PROG
don't save calibration
APLY
oUt
T
T
UP
UP
PROG
T
T
NORM
NORM
T
T
DOWN
DOWN
Corr
Corr
SET1
ON
REG
SET1
ON
REG
SET2
MAN
ALARM
SET2
MAN
ALARM
save calibration factor Y2
PROG
don't save calibration
APLY
oUt
T
T
UP
UP
PR OG
T
T
NORM
NORM
T
T
DOWN
DOWN
Corr
Corr
SET1
ON
REG
SET1
ON
REG
SET2
MAN
ALARM
SET2
MAN
ALARM
oUt
save calibration factor Y3
PROG
Corr
don't save calibration
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany
Calibration
Exit
PROG
Corr
oUt
PROG
see Appendix E
„Calibration"
Exit
T
PROG
UP
T
UP
T
T
NORM
NORM
T
T
DOWN
DOWN
tunE
SET1
ON
REG
SET1
ON
REG
SET2
MAN
ALARM
SET2
MAN
ALARM
Cancel
T
UP
T
NORM
T
DOWN
SET1
ON
REG
PROG
SET2
MAN
ALARM
T
UP
PROG
T
NORM
T
DOWN
tunE
SET1
ON
REG
SET2
MAN
ALARM
T
Autotuning successfully
UP
T
completed
NORM
T
DOWN
SET1
ON
REG
SET2
MAN
ALARM
T
PR OG
UP
T
NORM
T
DOWN
tunE
SET1
ON
REG
SET2
MAN
ALARM
Autotuning cannot be
successfully completed
inP.F = mAn1
P.ini = 0.0
P.ind = P
Measured
284.9
value
TUP
T
NORM
T
DOWN
285.0
Setpoint
SET1
ON
REG
SET2
MAN
ALARM
DI
0.0
TUP
T
NORM
T
DOWN
284.9
SET1
ON
REG
value
SET2
MAN
ALARM
Control signal
manipulation
100.0
TUP
T
NORM
T
DOWN
284.9
SET1
ON
REG
value
SET2
MAN
ALARM
DI
350.9
if inP.F = mAn2 then
TUP
value
T
NORM
Setpoint = last measu-
T
DOWN
285.0
SET1
ON
REG
red value
Setpoint
SET2
MAN
ALARM
back to menu
„Calibration"
factor Y1
factor Y2
factor Y3
Tel: +49 (0) 511 16 59 6720 ·
www.akytec.de