Installation
By default the outputs are assigned:
The output assignments and scales can be changed by Modbus commands.
As the humidity and temperature sensor module is located inside the enclosure and at-
tached to the motherboard, the sensors may be subject to transmitter self-heating effects.
If 4-20 mA or 0-10 V analog outputs are used, powering from 12 V DC voltage is recom-
mended for less self-heating of the instrument and achieving higher accuracy. If only
RS485 interface is used, 24 V DC supply voltage is also appropriate. For wiring of RS485
lines use twisted pair cable, like LiYY TP 2 x 2 x 0.5 mm
D+(A) and D-(B) wires and the second pair for common 0V and power +U wires.
After wiring and setting output options attach the enclosure back to the base.
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany · Tel.: +49 (0) 511 16 59 672-0 ·
OUT1: to relative humidity with default scale 0 - 95 % RH
OUT2: to temperature with default scale -20...+70 °C
2
or CAT 5. Use one pair for
www.akytec.de
7