Temperature Setting
(SEL Button Push for 3 Sec.)
No
Menu
001
Temperature Setting
Setting 1 Group
(PRG Button Push for 5 Sec.)
No
Menu
001
Type Select(※1)
002
Control Deviation
003
ON Delay Time(※2)
004
Min. OFF Time(※3)
005
Min. ON Time(※4)
006
Deviation Type(※5)
007
Set Value Max.
008
Set Value Min.
010
Natural Defrost Cycle(※6)
011
Natural Defrost Time(※7)
(※1) Select Control Type
: OFF = No use output function (Use display mode only.)
(※2) ON Delay Time
: Even under the output condition, it outputs after delay time which is set.
(During ON delay time, lamp flickers on a quick cycle and lights when it outputs.)
(※3) Min. OFF Time
: It does not output during minimum OFF time after OFF.
(During minimum OFF time, lamp flickers every second and lights when it outputs.)
(※4) Min. ON Time
: To prevent frequent ON/OFF of control outputs, it maintains ON status during minimum ON time after switching to ON even
under the OFF condition (immediately switching to OFF when error)
(※5) Deviation Type
: Select deviation type of control output.
e.g)Condition : Cooling mode, setting temp.10.0℃, deviation 1.0℃.
+Deviation control : ON at 11.0℃ , OFF at 10.0℃. ±Deviation control : ON at 10.5℃ , OFF at 9.5℃.
(※6) Natural Defrost Cycle : It is a time interval between defrost, and outputs without defrost for the set time.
e.g) If DEP is 300 minutes and DFT is 20 minutes, it outputs according to temp.
for 300 minutes, and defrost output works for 20 minutes.
(※7) Natural Defrost Time : It is time that real defrost output is working ※ Either of those two is OFF, natural defrost function is not work.
Setting 2 Group
(PRG Button Push for 10 Sec.)
No
Menu
400
Lock Function
401
Sensor Type
402
Unit of temperature
403
Point Display
404
Sensor Correction(※1)
406
Input Filter(※2)
407
Display Cycle
408
Error Occur Run Cycle(※3)
409
Error Occur Operation Rate(※4)
(※1) Correct Temp. Sensor
(※2) Input Filter
(※3) Error Occur Run Cycle
(※4) Error Occur Operation Rate : Input ON/OFF ratio of output at sensor error.
Code
Code
TYP
D IF
DLT
RT
NT
DTP
UH
UL
DFP
DFT
H = Use heating control only (Use UNDER temperature sensing only.)
Code
OFF : Lock Cancel
LOC
LC2 : Setting 1,2 Group Lock LC3 : All Setting value Lock
TH 1 : DPR-TH01 (-50~105°C)
IN
UNT
0. 1 : Decimal point display
DP
COR
FT
DT
CLE
DUT
: Correct the accuracy of the temp sensor.
e.g) If displayed temp. is 19℃ and measured temp. is 18℃, it is corrected by in putting -1.0℃.
: Set a sensor input filter value.
In case of frequent hunting of the current temp., it is corected by increasing filter value.
: Input ON/OFF cycle of output at sensor error.
e.g) If CLE is 20 Min., DUT is 10% the output at sensor error is OFF for 18 Min. and ON for 2Min.
※ No display in case of CLE OFF.
Unit
Step
°C
0.1
Unit
Step
: D i s p l a y
C : C o o l i n g
O F F
°C
0.1
sec
1
sec
1
sec
1
P (0) : +Deviation
PN (1): ± Deviation
°C
1
°C
1
Min
1
OFF (0)
Min
1
OFF (0)
C = Use cooling control only (Use OVER temperature sensing only.)
Unit
Step
Min.
LC 1 : Setting 1 Group Lock
TH2 : DPR-TH02 (-50~150°C)
oC : Celsius
oF : Fahrenheit
1 : Do not display decimals
°C
0.1
-99.9
sec
0.1
sec
0.1
min
1
%
1
- 4 -
Min.
Max.
UL
UH
Min.
Max.
H : H e a t i n g
0.1
99.9
0
999
0
999
0
999
UL
150
-50
UH
999
999
Max.
Default
OFF
TH1
oC
0. 1
99.9
0.0
0.1
5.0
0.5
0
5.0
1 .0
0
999
OFF
0
1 00
50
Default
CustomSetup
0.0
Default
CustomSetup
C
1 .0
5
0
5
P
1 00
-45
OFF
OFF
CustomSetup
R20160721