DOTECH EVC10B-00 Manual do utilizador - Página 8
Procurar online ou descarregar pdf Manual do utilizador para Controlador DOTECH EVC10B-00. DOTECH EVC10B-00 8 páginas. Electronic expansion valve controller
: TRIP / ALARM MESSAGE
Cods
Description
POP
Pressure sensor disconnection
PST
Pressure sensor Short circuit
TOP
Pressure sensor disconnection
TST
Pressure sensor Short circuit
Detect MOP temperature
MOP
Detect lower limit Pressure alarm
LOP
Detect high Superheat alarm
HSH
Detect low superheat alarm
LSH
Detect freezing Protection alarm
FRE
※ Alarm which is flickering needs to reset by manual.
※ Press PRG/RST button two times quickly. Auxiliary relay (RL1) will be outputted if alarm is occurred. (In case of setting for alarm output relay)
6.
Communication Protocol
: Specifications of communication
Item
Description
Transmission line connection
Multiple line
Communications method
RS485 (2-wire, half-duplex)
Baud-rate
BPS default 9600 BPS
Parity, Data, Stop bit
None, 8 Data, 1 Stop
Protocol Type
Modbus RTU MODE
Function Code
Read HOLD REGISTERS (0x03) / Preset Single Register (0x06)
Maximum Read Word
32 Word
Media Type
BELDEN 9841 / 9842, LG LIREV-AMESB
Poll interval
100msec
: STATUS - Communication Table
Address
Function
4 0073
EEV compulsory open ratio(※1)
4 0099
Reset command
4 0101
Run / Stop input (※2)
4 0102
Operation status
Bit0
Operation status of EEV
Bit1
Aux. relay output
4 0110
Alarm status
Bit0
Press. sensor disconnection
Bit1
Press. sensor short circuit
Bit2
Temp. sensor disconnection
Bit3
Temp. sensor short circuit
Bit4
MOP alarm
Bit5
Lower limit pressure alarm
Bit6
High superheat alarm
Bit7
Low superheat alarm
Bit8
Freezing protection alarm
4 0111
Present Superheat
4 0112
Present saturation temperature
4 0113
Present pressure
4 0114
Present temperature
4 0116
EEV open ratio
(※1) Manual control of EEV by communication
Electronic expansion valve will be controlled manually regardless of superheat of present system just by using 0.0 to 100.0% of UCR (electronic expansion valve compulsory open ration)
To lift a UCR (electronic expansion valve compulsory open ration), please input '1' at 4 0073. Then it will be converted into automatic control mode.
But, electronic expansion valve will be closed automatically at the status of stop or alarm
(※2) Run / Stop by communication
※ RMT(Run/Stop) : It will be run or stopped by input of 4 0101 only if run / stop method should be set to communication (2)
Parameter
-
If pressure sensor is disconnected
-
If pressure sensor is short circuited
-
If temperature sensor is disconnected
-
If temperature sensor is short circuited
MP= 1
If present pressure remains higher than set value of MOP
MP= 2 (Flickering)
during MPD (MOP alarm detection delay time)
LP= 1
If present pressure remains lower than set value of LOP
LP = 2 (Flickering)
during LDP (Low limit pressure alarm delay time)
HS= 1
If present super heat remains higher than set value of HSH
during HSD (High superheat alarm delay time)
HS = 2(Flickering)
LS= 1
If present super heat remains lower than set value of LSH
LS = 2(Flickering)
during LSD (Low superheat alarm delay time)
FR= 1
If present temperature remains lower than set value of FRE
FR= 2(Flickering)
during FRD (Freezing protection alarm delay time)
Unit
Type
%
Analog
-
Analog
-
Analog
-
Analog
-
Digital
-
Digital
-
Analog
-
Digital
-
Digital
-
Digital
-
Digital
-
Digital
-
Digital
-
Digital
-
Digital
-
Digital
K
Analog
℃
Analog
bar
Analog
℃
Analog
%
Analog
Conditions for occurrence
Size (Word)
EVC10B
INT 16
0.0 - 100.0
INT 16
0 : OFF
INT 16
0 : Stop
INT 16
Bit
0 : OFF
Bit
0 : OFF
INT 16
Bit
0 : OFF
Bit
0 : OFF
Bit
0 : OFF
Bit
0 : OFF
Bit
0 : OFF
Bit
0 : OFF
Bit
0 : OFF
Bit
0 : OFF
Bit
0 : OFF
INT 16
INT 16
INT 16
-1.0 ~ 1.0
INT 16
-100.0 100.0
INT 16
0.0 - 100.0
-8-
Ways to clear
If pressure sensor is normal
If temperature sensor is normal
System check is needed
It becomes a clear condition if present pressure value is less
than set value of MPF
It will be caused by lack of refrigerant.
It becomes a clear condition if present pressure is more than
set value of LPF
System check is needed
It becomes a clear condition if preset super heat is less than
set value of HSF
System check is needed
It becomes a clear condition if present super heat is more
than set value of LSF
Evaporator temperature is low. System check is needed It
becomes a clear condition if present temperature is more
than set value of FRF.
MMI
X 10
1 : ON
1 : Run
Refer to below bit
1 : ON
1 : ON
Refer to below bit
1 : ON
1 : ON
1 : ON
1 : ON
1 : ON
1 : ON
1 : ON
1 : ON
1 : ON
X 10
X 10
X 10
X 10
X 10
EVC10B R20140821