DOTECH FX3S Series Manual do utilizador - Página 2

Procurar online ou descarregar pdf Manual do utilizador para Controlador DOTECH FX3S Series. DOTECH FX3S Series 2 páginas. Multi digital temp controller

DOTECH FX3S Series Manual do utilizador
Setting 1 Group
Display Current Temperature
Run mode
Push for 3 Sec.
Push for 3 Sec.
Setting 1 Group Table
No
CODE
DESCRIPTION
001
Type Select
002
Control Deviation
003
ON Delay Time
004
Min. OFF Time
005
Min. ON Time
006
Deviation type
007
Set Value Max.
008
Set Value Min.
110
Defrost Cycle
111
Defrost Time
Select Control Type
Set control function of control output.
No use output function
(Use display mode only.)
Use cooling control only
(Use OVER temperature sensing only.)
Use heating control only
(Use UNDER temperature sensing only.)
Control Deviation Value
Set control sensitivity of control output.
Setting Range 0 ~ 19.9℃.
ON Delay Time
Output after delaying during setting delay time
in case of control output ON.
Minimum OFF Time
No output within Min. OFF time
after control output OFF.
Minimum ON Time
Maintain ON in spite of OFF condition
during Min. ON time after ON.
Select Deviation Type.
Select deviation type of control output.
+
Deviation control
±
Deviation control
e.g)Condition : Cooling mode, setting temp.10.0℃,
deviation 1.0℃.
+Deviation control : ON at 11.0℃ , OFF at 10.0℃.
±Deviation control : ON at 10.5℃ , OFF at 9.5℃.
Max. Set Point
Set a maximum value of the set temperature
available to be set by user.
Min. Set Point
Set a minimum value of the set temperature
available to be set by user.
Natural Defrost Cycle
It is a time interval between defrost, and outputs
without defrost for the set time.
e.g) If DEP is 300 minutes and DFT is 20 minutes, it
outputs according to temp. for 300 minutes, and
defrost output works for 20 minutes.
Natural Defrost Time
It is time that real defrost output is working
※ Either of those two is OFF, natural defrost
function is not work.
UNIT
STEP
MIN
MAX
DEFAULT
(Display)
(Cooling)
(Heating)
0.1
0.1
99.9
1.0
Sec
1
0
999
Sec
1
0
999
Sec
1
0
999
(+Deviation)
(±Deviation)
1
150
100
1
-50
-45
Min
1
0
999
Min
1
0
999
Temperature Setting Group
Run Mode
If there's no input made for a period of 60 seconds during the setting,
then it return back to the run mode automatically.
Setting 2 Group
Run Mode
Push for 3 Sec.
Setting 2 Group Table
NO
CODE
400
5
401
0
403
5
404
406
407
408
409
Display Current Temperaure
Push for 3 Sec.
● The set point is indicated by flickering at every 0.5 seconds intervals,
and this set point can be established by using the ▲key or ▼ key.
● After establishing a set point, if you press the SEL key, it returns
back to next mode changed as the set point is stored.
Display current temperature.
Lock Function
Push for 5 Sec.
Select lock function.
LOCK cancel
Setting 1 group LOCK
Setting 1,2 group LOCK
Setting 1,2 Group, setting temp LOCK
Type of Sensor
Select the type of temperature sensor.
Use DPR-TH1 sensor.
(Range: -50~105
Use DPR-TH2 sensor.
(Range: -50~150
Decimal Point Display
Select temp display method.
Display 1st decimal place.
No display decimal points.
Correct Temp. Sensor
Correct the accuracy of the temp sensor.
e.g) If displayed temp. is 19
18
, it is corrected by in putting -1.0
Input Filter
Set a sensor input filter value.
In case of frequent hunting of the current temp.,
it is corected by increasing filter value.
Display Cycle
10
Input the display cycle for the current temp. value.
Operational Cycle at error Occurrence.
Input ON/OFF cycle of output at sensor error.
e.g) If CLE is 20 Min., DUT is 10% the output
at sensor error is OFF for 18 Min. and ON for 2Min.
Operational Rate at error occurrence
Input ON/OFF ratio of output at sensor error.
No display in case of CLE OFF.
DESCRIPTION
UNIT
STEP
: Lock Cancel
: Setting 1 Group Lock
LOCK FUNCTION
: Setting 1,2 Group Lock
: All Setting value Lock
: DPR-TH1 (-50~105℃)
Sensor Type
: DPR-TH2 (-50~150℃)
0.1 : 0.1
Point Display
K
0.1
Sensor Correction
Sec.
0.1
Input Filter
Sec.
0.1
Display Cycle
Min.
1
Error Occur Run Cycle
%
1
Error Occur Operation Rate
)
)
and I/O temp. is
.
MIN
MAX
DEFAULT
1 : 1
0. 1
-19.9
+19.9
0.0
0.1
10.0
0.5
0.0
5.0
1.0
1
20
1
100
5 0
2