Baumer AMG11 N13 Manual - Página 23
Procurar online ou descarregar pdf Manual para Conversor de multimédia Baumer AMG11 N13. Baumer AMG11 N13 41 páginas. Absolute encoders with profinet interface
Example for parameters with endless operation:
Maximum possible revolutions
Measuring units per revolution
Total measuring range
Calculation:
4.7. Implementation of system functions for alarm handling
Make sure that the system components required for alarm handling have been implemented in the project. To
Siemens Step7 projects apply in particular OB82 ("I/O Point Fault") and OB86 ("Loss Of Rack Fault"). Missing
these components will result in a PLC to STOP in case of alarm.
4.7.1.
I/O Point Fault - OB
The encoder supports the follwing channel related diagnostic alarms:
Alarm
Battery low (*)
Position error
Parameter error (*)
Basic encoder error – communication (analog) (*)
Basic encoder error – communication (digital) (*)
Preset error: value out of range
(*) Channel-specific diagnostics in the event of error is already present during encoder bootup.
4.7.2.
Loss Of Rack Fault - OB
Loss Of Rack Fault OB (OB86) is triggered when the encoder is available on the bus after bootup („outgoing
event) or when being no longer accessible (switched off or disconnected from the bus, „incoming event").
4.8. Compilation and load of hardware and software configuration
After complete hardware project configuration and once having entered all parameters the project must be
compiled ("translated") and exported to the PLC.
4.9. Restore Factory Defaults
The projecting tool may be used to restore encoder settings to the factory default values. Preparations and
proceedings are described in chapter 5.3 "Device name assignment". Click button „Reset" in Field "Reset to
Factory Settings" as shown in 5.3.3. The restore operation must be followed up by encoder power off and on.
The entire customer-specific configuration including device name and IP will be deleted. Only MAC-ID and
serial number are retained.
Note: The device name being deleted may make the PLC immediately try to allocate the projected name
again. If this is unwanted, automated name allocation should be disabled in project „Device exchange without
removable media" prior to executing the Factory Setup.
Baumer_BUDE-PROFINET_MA_EN.docx
14.06.2016 / bja
65536
(16 bit multiturn)
3600
100.000
65536 x 3600 / 100.000 = 2359 remainder 29600
Error
Number
20 (14h)
22 (16h)
26 (1Ah)
28 (1Ch)
29 (1Dh)
30 (1Eh)
23/41
www.baumer.com