Baumer HUBNER BERLIN Proibus DP HMG 10 Manual de instruções de instalação e funcionamento - Página 19
Procurar online ou descarregar pdf Manual de instruções de instalação e funcionamento para Conversor de multimédia Baumer HUBNER BERLIN Proibus DP HMG 10. Baumer HUBNER BERLIN Proibus DP HMG 10 32 páginas. Absolute encoder with magnetic sensing
![Baumer HUBNER BERLIN Proibus DP HMG 10 Manual de instruções de instalação e funcionamento](/uploads/products/server2/1260694/1260694.jpg)
View in bus connecting box Proibus DP [A]
5.1.4
Terminal assignment
A
B
UB
GND
Terminals of the same signiicance are internally connected and identical in their
i
functions. Max. load on the internal terminal connections UB-UB and GND-GND
is 1 A each.
5.1.5
Setting for the terminating resistors
ON = Last user
OFF = User xx
5.1.6
Setting for the user address
Address can be set by rotary switches. Example: User address 23
MB246EN - 11171695, 16A3, Baumer_HMG10-ProibusDP_II_EN
Negative serial data transmission, pair 1 and pair 2
Positive serial data transmission, pair 1 and pair 2
Voltage supply 10...30 VDC
Ground for UB
ELECTRICAL CONNECTION / PROFIBUS DP
Setting for the terminating resistors
Setting for the user address
16/29