Programmable LitePak Panels
LitePak Panel
8 or 16 relays
H
120/277V
Breaker
20A Relays
Lights
Max 4 relays per
control output.
Trans-
former
B l u
W h
1
4
2
5
6
3
Optional Remote Switches
Connect standard Douglas switches
direct to relays for remote override.
Group switch input on the controller
can control some or all of the relays.
PART NUMBERS
WPAK-33518-S* 120/277V LitePak Panel c/w 8 relays & Controller Module
LitePak Expansion Panel c/w ONLY 8 relays
WPAK-33018-S*
WPAK-33318-S*
120/347V LitePak Panel c/w 8 relays & Controller Module
277/480V LitePak Pnl c/w 4 - 2p Relays & Controller
WPAK-33524-S*
WPAK-33024-S*
277/480V LitePak Expansion Panel c/w ONLY 4 - 2p Relays
WPAK16-3351-S* 120/277V LitePak Panel c/w 16 relays & Controller Module
WPAK16-3331-S* 120/347V LitePak Panel c/w 16 relays & Controller Module
WPAK16-3352-S*
277/480V LitePak Pnl c/w 8 - 2p Relays & Controller
LitePak Expansion Panel c/w ONLY 16 relays
WPAK16-3301-S*
WPS-5527K
Remote Photometric Sensor
Switches
All models of Douglas 2wire relay switches
* Suffix Definitions: -S = Surface Cover, -F = Flush Cover
Components 7.3
B-7.1,2,3,4 -Auto, LitePak Panels
Optional Remote
N
Photo Sensor
Sensor range:
0 to 6,500 fc (±5%).
LitePak
Controller
A
B
C
D
1
2
3
1
2
3
E s c
C l r
4
5
6
4
5
6
8
7
9
0
8
7
9
0
S e n s o r
S e n s o r
G r o u p
1
2
3
4
5
6
7
8
B l u
W h
W h
W h
Expansion Panel Bus
Eleven (11) conductors
will ensure that all
switching combinations
are possible.
www.DouglasLightingControls.com
L i t e P a k
CONNECTIONS
Detailed Schematic Example
n
The schematic shows an 8-relay LitePak installation that utilizes
all of the options possible. In addition, the switching groups are
altered slightly from the standard factory connections to illustrate
grouping several relays on an output.
n
Relays 1,2,3 and 4 of the main panel are the factory connections.
Relays 5,6,7 and 8 of the main panel are all connected to
controller output #5 and they switch together.
n
The expansion panel has 3 groups of relays that are switched by
controller outputs #1, #2 and #6. Note that 11 conductors connect
the expansion panel to the main panel even though all conductors
are not used. This permits all possible switching combinations and
permits switch stations to be connected to the expansion panel.
n
The WPS-5527K photo sensor connects with 2 wires to the controller.
n
The primary connection of the transformer (wiring not shown) is
wired for a 277V connection. If connecting 120V, connect the
120V wire of the transformer to the terminal block.
Caution: Do not connect 277V to the 120V wire of the transformer
as the over voltage will damage the LitePak controller.
LitePak Expansion Panel
8 relays
H
120/277V
Breaker
20A Relays
Lights
Max 4 relays per
control output.
Technical Data
1
2
3
4
5
6
7
8
B l u
W h
W h
W h