3.5 Key-Switch Installation

E X T I N G U I S H A N T
R E L E A S E
R E L E A S E D
I M M I N E N T
T I M E R H E L D
A B O R T E D
F A U L T
D I S A B L E D
M O D E
A U T O +
M A N U A L O N L Y
M A N U A L
4 8 5 - I N
S U P P L Y
I N P U T S
C O N T R A S T
A D J U S T
Using a sharp knife, cut through the fascia label using the key-switch mounting hole as a template.
Insert the key-switch assembly through the hole and secure with the fixing nut. Before fully tightening, insert the
slide-in label with the required function description into the pocket in the fascia label.
Plug the connector into the respective connector on the card.
Key-Switch assemblies are available in both trapped and non-trapped versions.
The function / action of the key-switch is defined in the control panel. Refer to the control panel manual for
further details.

3.6 Adjusting the LCD Contrast / Address setting

Press the CONTRAST ADJUST button. This display will show the contrast adjust option.
[RSI Address Setup]
THIS ADDRESS: 1
www.advancedco.com
F I R E
Z O N E - 1
R e m o t e S t a t u s I n d i c a t o r
Z O N E - 2
Z O N E - 3
S Y S T E M F A U L T
U S B
4 8 5 - O U T
R U N P R O G
R E B O O T
S W I T C H
Use the  buttons to adjust the contrast (viewing angle) darker
or lighter as required. The bar graph adjusts to show the contrast
setting.
Press the  button to confirm the setting.
The display will then show the unit address.
Use the  buttons to adjust the address as required.
Press the  button to confirm the setting.
The display will then revert to the normal operating display.
SLIDE-IN LABEL
Key-Switch Assembly
Nut
PL1
PL3
PL2
PL2: KEY-SW
PL3: 2-Way Relay Card
PL1: Manual Trigger
17