Power factor (cos φ) regulator
model HPR6, HPR12
Installation and user manual

Installation

Verify that the regulator supply voltage is
consistent with the voltage of the power grid
(90 .. 550V). The power factor correction
regulator shall be wired as shown in the
diagram below, with the short circuit protection
fuses as shown, size 10 A.
Description of the terminals:
 S1 and S2: wires k and l (L lowercase)
from the secondary coil of the current
transformer (CT) installed on the phase
L1 (R).
 U1 and U2: regulator power supply and
voltage measurement.
 C: common terminal of the bank control,
that has to be protected with a fuse of
size 10 A.
 1, 2, ..., n: capacitor banks control.
MU 03.21 IT EN rev.1 ed. 5/2017
)
SW rev.2.02
Cod. 381025
Programming
From the main menu, press the key ▼ till the
message SETUP appears on the right side of
the display. Then press the key ► to enter.
The SETUP menu is structured in 7 submenus
(100 – 700). Only the menu 100 can be
reached by pressing the button ►( ) without
PIN. You go into in the next menus only by
entering a PIN code (default 242). Pressing ▲
and ▼ the submenus or the parameters are
selected. Pressing ►(
submenus
or
you
modification mode. Pressing ◄ (esc) you
return to the upper level. The main menu is
reached by pressing the key ◄ (esc) many
times until the display shows only the power
factor.
In parameter modification mode, the cursor
blinks. Pressing ▲ and ▼ the values on the
cursor can be changed, pressing ◄ and ► the
cursor can move.
To save changes, you must press ►(
the cursor is on the right.
To undo the changes the key ◄ (esc) can be
pressed when the cursor is on the left.

Menu structure

The table shows an overview of the regulator
parameters. Menu programming from 200 to
600 must only be made using the reference
manual.
Menu 100
Un
Nominal voltage (required for
monitoring the minimum and maximum
voltage levels and as reference for the
parameter store of the regulator)
Ct
CT ratio (when not set, all
measurements are hidden)
Pt
PT ratio
) you enter the
enter
the
parameter
) when