2.4.1 Class A Conventional Zone Wiring

1. Wire out-going conventional zone circuit wiring to "Zone 1, 2, 3 or 4, OUT + and –". Wire incoming
conventional zone circuit wiring to "Zone 1, 2, 3 or 4, IN + and –"(see figure 8).

2.4.2 Class B Conventional Zone Wiring

1. Wire out-going conventional zone circuit wiring to "Zone 1, 2, 3, 4, 5, 6, 7 or 8, OUT + and –", and install
a 6.8K end-of-line (EOL) resistor (4.7K or 3.9K based on DIP switch 1 and 2 setting) at the last device
(see figure 9).
10
Figure 8 – AX-CZM Class A Module Wiring
Figure 9 – AX-CZM Class B Module Wiring