Module Specifications

AX–CZM Conventional Zone Module Specifications
Operating Voltage
Operating Current
Quiescent
Minimum
Maximum (Relays - OFF)
Maximum (Relays - ON)
Alarm
Ground Fault Reference Impedance
Temperature (Indoor/Dry Environment)
Relative Humidity
Dimension
Weight
Zone Circuits
Zone Circuit Voltage
Zone Circuit Current Limit
Zone Circuit Resistance
Class B End-of-Line (EOL)
As our policy is one of constant product improvement the right is therefore reserved to modify product specifications without prior notice
www.advancedco.com
www.advancedco.com
24VDC (wired from FACP 24VDC or a Listed power supply)
110mA (Vs = 24V, 8 Zones = Min Load)
120mA (Vs = 24V, 8 Zones = Max Load, Relays Off)
135mA (Vs = 24V, 8 Zones = Max Load, 3 Relays On)
@ least 318mA (Vs = 20V, 8 Zones = Max Alarm Load, 3 Relays On)
75K (valid only for AX-CZMs performing earth/ground fault detection)
0
0
32–120
F (0-49
C)
93% Non Condensing (maximum)
1.3"H x 4.2"W x 5"L
5.3 oz
Eight (8) Class B or Four (4) Class A
24V ± 5%
50mA (Under Short Circuit)
50Ω
Configurable:
6.8K, Part Number 855-027-682
4.7K, Part Number 855-027-472
3.9K, Part Number 855-027-392
End-of-line resistors for the Canadian CAX-CZM must be installed on
an Advanced EOL-ASSY (standard single gang end-of-line plate)
17