Advanced Ex-3021 Manual - Página 6
Procurar online ou descarregar pdf Manual para Instrumentos de medição Advanced Ex-3021. Advanced Ex-3021 20 páginas. Remote status indicators
2.1.1.2 LED Indications
The LED Status Indications show the basic operational state of the panel and whether the panel is in a fire
alarm, fault, disabled or test condition.
2.1.1.2.1 GENERAL STATUS
Function
SYSTEM FAULT
2.1.1.2.2 DETECTION ZONE STATUS
Function
FIRE
2.1.1.2.3 EXTINGUISHANT
Function
RELEASE IMMINENT
RELEASED
TIMER HELD
ABORTED
DISABLED
FAULT
MANUAL ONLY
AUTO + MANUAL
2.1.1.3 Manual Release Button (Ex-3030 Only)
To manually release the extinguishant, pull down the flap and press the button marked with the circle.
6
Colour
Description
Indicates the presence of a system fault
Yellow
Colour
Description
Indicates that the system has detected a fire alarm condition in the respecitve zone
Red
Colour
Description
Indicates (flashing) that the release of extinguishant is imminent. The indication will turn to
Red
steady when the signal to release the extinguishant has been activated.
Indicates that the release of extinguishant has occurred and the panel has detected the folw
Red
of the extinguishant released.
Indicates that the imminent release of extinguishant is temproraily suspended.
Yellow
Indicates that the imminent release of the extinguishant has been aborted.
Yellow
Indicates that the extinguishant release control signal has been disabled. The release of
Yellow
extinguishant is prevented even if a fire alarm or manual release are present.
Indicates that the system has detected a fault condition within part of the extinguishing
Yellow
system and control device (ECD) circuits.
Indicates that the extinguishant can only be released by means of a manual release button.
Yellow
Indicates that the extinguishant can be released by both the automatic detection of a fire
Yellow
alarm and by means of a manual release button.
www.advancedco.com