Specifications & Ordering:
Models, Sales Order Parts:
Part No:
Mxp-029 : Shop Interface Unit
Applications / Limitations:
Inputs
Input A : Monitored switch input.
Input B : Monitored switch input.
Input C : Pulse/Continuous detecting input.
Input D : Clean contact switch input.
Input E : Clean contact switch input.
Outputs
Relay 1 : Volt-free Normally open relay contacts
Relay 2 : Volt-free Normally open relay contacts
The Interface is used in place of the standard MXP-014 8-way input board (i.e. don't attempt to fit both units to
the same chassis).
Compatibility:
The Shop Interface unit mounts in the MxPro 4 panels as follows:
Mx-4200, Mx-4400 & Mx-4800 control panels – directly onto the chassis.
Mx-4100/L control panel – on the rear face of the back box.
This interface is supported from panel software revision 016 onwards.
Item
Panel loading, quiescent state
Panel loading, all inputs activated. Relays
off.
Panel loading, all inputs activated. Relays
energised.
Relay Contact Rating
Maximum Working Temperature
As our policy is one of constant product improvement the right is therefore reserved to modify product specifications without prior notice
www.acornfiresecurity.com
Specification Details
12mA
22mA
34mA
1 Amp 30V DC/AC max
50°C