3.3.1 Single outdoor unit installation
When the upward area is open (Unit: mm)
(1) Obstacles at rear only
150
(3) Obstacles at front only
1000 or more
When an obstruction is present also in the upward area (Unit: mm)
(1) Obstacles at rear and above only
1000
300
Max. 500
3.3.2 Multiple outdoor unit installation
• Provide at least 25 mm of space between the outdoor units if multiple units are installed.
• When routing the piping from the side of an outdoor unit, provide space for the piping.
• No more than 3 units must be installed side by side.
When 3 units or more are arranged in a line, provide the space as shown in the following
example when an obstruction is present also in the upward area.
When the upward area is open (Unit: mm)
(1) Obstacles at rear only
300
(3) Obstacles at front and rear only
When an obstruction is present also in the upward area (Unit: mm)
• Obstacles at rear and above only
1500
(2) Obstacles at rear and sides only
200
300
200
(4) Obstacles at front and rear only
150
1000 or more
(2) Obstacles at rear, sides, and above only
1500
500
250
Max. 500
250
(2) Obstacles at front only
1500 or more
500
1500 or more
1500
500
Max. 300
3.3.3 Outdoor units installation in multi row
* The following settings are not recommended in case of cooling by a low outside tem-
perature. (Unit: mm)
(1) Single parallel unit arrangement
150
2000 or
more
600
1000
3.4. Transporting the unit
Do not touch the fi ns. Otherwise, personal injury could result.
When carrying the unit, hold the handles on the right and left sides and be careful.
If the outdoor unit is carried from the bottom, hands or fi ngers may be pinched.
• Carry slowly in the manner as shown on "Fig. B" holding the handles "Fig. A" in right and
left sides. (Be careful not to touch with hands or objects.)
• Be sure to hold the handles on the sides of the unit. Otherwise, the suction grilles on the
sides of the unit may be deformed.
Fig. A
Suction grille
Handle
Handle
3.5. Installing the unit
• Please install the outdoor unit without slant. (within 3 degrees )
• Install 4 anchor bolts at the locations indicated with arrows in the fi gure.
• To reduce vibration, do not install the unit directly on the ground. Install it on a secure
base (such as concrete blocks).
• The foundation shall support the legs of the unit and have a width of 50 mm or more.
• Depending on the installation conditions, the outdoor unit may spread its vibration during
operation, which may cause noise and vibration. Therefore, attach damping materials
(such as damping pads) to the outdoor unit during installation.
• Install the foundation, making sure that there is enough space for installing the connec-
tion pipes.
• Secure the unit to a solid block using foundation bolts. (Use 4 sets of commercially avail-
able M10 bolts, nuts, and washers.)
• The bolts should protrude 20 mm. (Refer to the fi gure.)
• If overturning prevention is required, purchase the necessary commercially available
items.
166
650
50
50
AIR
Do not install directly on the ground, this may result in equipment failure.
Provide ample space for ice buildup from condensate between the bottom of the unit and
the fl at surface on which it is mounted.
Otherwise, there is risk that the drainage water will freeze between the device and the
surface, disabling drainage.
If the unit is installed in a region that is exposed
to high winds, freezing conditions, freezing rain,
snow fall or heavy snow accumulation, take
appropriate measures to protect it from those ele-
ments.
To ensure stable operation, the outdoor unit must
be installed on a raised stand or rack, at or above
the anticipated snow depth for the region.
The installation of snow hoods and drift preven-
tion fencing is recommended when blowing and
drifting snow is common to the region.
Base
(2) Multiple parallel unit arrangement
3000 or
more
600
1500
WARNING
CAUTION
Fig. B
Front view
Rear view
Unit: mm
154
Bolt
Nut
Base
CAUTION
500