AirStage ASUB18RLAV Manual de instalação - Página 14

Procurar online ou descarregar pdf Manual de instalação para Ar condicionado AirStage ASUB18RLAV. AirStage ASUB18RLAV 17 páginas. Indoor unit (wall mounted type)
Também para AirStage ASUB18RLAV: Manual de instruções (8 páginas)

AirStage ASUB18RLAV Manual de instalação
7.3.1. Button name and function
OPERATION indicator lamp (Green)
TIMER indicator lamp (Orange)
FILTER indicator lamp (Red)
7.3.2. Checking the function settings
• Press and hold the "MANUAL AUTO" button on the indoor unit for 3 seconds to check
the function settings. It is necessary to disconnect the power in order to return to normal
operation mode.
(1) Indoor unit and refrigerant address indication
Indication pattern
Indicator name
Indoor unit address
OPERATION
ON
indicator lamp (Green)
TIMER indicator
Address: tens place (0.5 s ON/0.5 s OFF)
lamp (Orange)
FILTER indicator
Address: ones place (0.5 s ON/0.5 s OFF)
lamp (Red)
• Indoor unit address example
(Example) ADDRESS : 24
OPERATION
ON
indicator lamp
(Green)
OFF
TIMER
ON
indicator lamp
0.5s 0.5s 0.5s 0.5s
(Orange)
OFF
ON
FILTER
0.5s 0.5s 0.5s 0.5s 0.5s 0.5s 0.5s 0.5s
indicator lamp
OFF
(Red)
• Refrigerant address example
(Example) ADDRESS : 30
OPERATION
ON
indicator lamp
1.0s
1.0s
(Green)
OFF
TIMER
ON
indicator lamp
0.5s 0.5s 0.5s 0.5s 0.5s 0.5s
(Orange)
OFF
ON
FILTER
indicator lamp
OFF
(Red)
• Setting details
Function
number
01
Indoor unit address
02
Refrigeration address
For use with a remote control, set all rotary switches to 0, and refer to "7.1. Setting the ad-
dress" for details.
All switches are set to 0 at the factory.
(2) Others
Indication pattern
Indicator Name
OPERATION indicator lamp (Green)
TIMER indicator lamp (Orange)
FILTER indicator lamp (Red)
En-13
Indication pattern
Refrigerant address
Flash (1.0 s ON/1.0 s OFF)
1 cycle 12 sec
ON
10 sec
8 sec
1 cycle 12 sec
1.0s
1.0s
1.0s
1.0s
1.0s
9 sec
OFF
Item
Setting number
00~63
00~99
Indication pattern
Function number; tens place (0.5 s ON/0.5 s OFF)
Function number; ones place (0.5 s ON/0.5 s OFF)
Setting number: (0 - 9) (0.5 s ON/0.5 s OFF)
(Example) Function : 31, Setting number : 2
OPERATION
ON
indicator lamp
0.5s
0.5s
0.5s
0.5s 0.5s 0.5s
(Green)
OFF
ON
TIMER
indicator lamp
0.5s 0.5s
(Orange)
OFF
ON
FILTER
0.5s
0.5s
0.5s
0.5s
indicator lamp
(Red)
OFF

8. FINISHING

Before performing this section, perform a sealing test. (Refer to the installation Manual for
the outdoor unit.)
] 1

8.1. Connection pipe, cable and drain hose

Insulate the drain hose, if necessary, to prevent it from freezing.
(1) Insulate between pipes.
• For
1
Rear,
2
Right and
3
Bottom piping, overlap the connection pipe heat insulation
and indoor unit pipe heat insulation and bind them with vinyl tape so that there is no
gap.
• For
4
Left bottom piping,
5
Left piping,
the connection pipe heat insulation and indoor unit pipe heat insulation together and
bind them with vinyl tape so that there is no gap.
( 1 Rear, 2 Right and 3 Bottom piping)
Overlap the insulation.
Connection pipe
(heat insulation)
Bind the pipes together so
that there is no gap.
(For
4
Left bottom piping,
5
Left piping,
• Wrap the area which accommodates the rear piping housing section with cloth tape.
• Bind the connection cable with vinyl tape.
• Bundle the piping and drain hose together by wrapping them with cloth tape over the
range within which they fi t into the rear piping housing section.
Connection pipe
Cloth tape
(Accessories)
Connection cable (Power supply cable)
Vinyl tape
Connection cable (Transmission and Remote controller cable)
Wrap with cloth tape
Pipe
Cloth tape
Drain hose
(2) Temporarily fasten the connection cable along the connection pipe with vinyl tape.
(3) Fasten the connection pipe to the outside wall with a saddle, etc.
(4) Fill the gap between the outside wall pipe hole and the pipe with sealer so that rain
water and cannot blow in.
(5) Fasten the drain hose to the outside wall, etc.
1 cycle 12 sec
9 sec
11 sec
10 sec
6
Center piping and
7
Left rear piping, butt
Indoor unit pipe (heat insulation)
Vinyl tape
6
Center piping and
7
Left rear piping)
Indoor unit pipe
Wrap with cloth tape.
Pipe