AirStage AUXM030GLEH Manual de instalação - Página 5

Procurar online ou descarregar pdf Manual de instalação para Ar condicionado AirStage AUXM030GLEH. AirStage AUXM030GLEH 13 páginas.

AirStage AUXM030GLEH Manual de instalação
3.3.4. Leveling
• Using a level, or vinyl hose
filled with water, fine adjust
so that the body is level.
• Inclined installation so
as the drain pipe side
is higher may cause a
malfunction of the float
switch, and may cause
water leakage.

4. PIPE INSTALLATION

Be more careful that foreign matter (oil, water, etc.) does not enter the piping than with
refrigerant R410A models. Also, when storing the piping, securely seal the openings by
pinching, taping, etc.
While welding the pipes, be sure to blow dry nitrogen gas through them.

4.1. Selecting the pipe material

Do not use existing pipes from another refrigeration system or refrigerant.
Use pipes that have clean external and internal sides without any contamination which
may cause trouble during use, such as sulfur, oxide, dust, cutting waste, oil, or water.
It is necessary to use seamless copper pipes.
Material : Phosphor deoxidized seamless copper pipes
It is desirable that the amount of residual oil is less than 40 mg/10 m.
Do not use copper pipes that have a collapsed, deformed, or discolored portion (es-
pecially on the interior surface). Otherwise, the expansion valve or capillary tube may
become blocked with contaminants.
Improper pipe selection will degrade performance. As an air conditioner using R410A
incurs pressure higher than when using conventional (R22) refrigerant, it is necessary to
choose adequate materials.
• Thicknesses of copper pipes used with R410A are as shown in the table.
• Never use copper pipes thinner than those indicated in the table even if they are avail-
able on the market.
Thicknesses of
Pipe outside diameter [mm (in)]
Annealed Copper
Pipes (R410A)

4.2. Pipe requirement

Refer to the installation manual for the outdoor unit for description of allowable pipe
length and height difference.
Use pipe with water-resistant heat insulation.
Install heat insulation around both the gas and liquid pipes. Failure to do so may cause
water leaks.
Use heat insulation with heat resistance above 120 °C. (Reverse cycle model only)
In addition, if the humidity level at the installation location of the refrigerant piping is
expected to exceed 70 %, install heat insulation around the refrigerant piping. If the
expected humidity level is 70 to 80 %, use heat insulation that is 15 mm or thicker and
if the expected humidity exceeds 80 %, use heat insulation that is 20 mm or thicker. If
heat insulation is used that is not as thick as specified, condensation may form on the
surface of the insulation. In addition, use heat insulation with heat conductivity of 0.045
W/(m·K) or less (at 20 °C).

4.3. Flare connection (pipe connection)

Tighten the flare nuts with a torque wrench using the specified tightening method. Other-
wise, the flare nuts could break after a prolonged period, causing refrigerant to leak and
generate hazardous gas if the refrigerant comes into contact with a flame.
Vinyl hoses
CAUTION
CAUTION
Thickness [mm]
6.35 (1/4)
0.80
9.52 (3/8)
0.80
12.70 (1/2)
0.80
15.88 (5/8)
1.00
19.05 (3/4)
1.20
CAUTION
CAUTION
WARNING
4.3.1. Flaring
Use special flare tool exclusive for R410A.
Drain pipe
(1) Cut the connection pipe to
the necessary length with a
pipe cutter.
(2) Hold the pipe downward so
that cuttings will not enter the
pipe and remove any burrs.
(3) Insert the flare nut (always
use the flare nut attached to
the indoor and outdoor units
(or RB unit) respectively)
onto the pipe and perform
the flare processing with a
flare tool. Use the special
R410A flare tool. Leakage of
refrigerant may result if other
flare nuts are used.
(4) Protect the pipes by pinching
them or with tape to prevent
dust, dirt, or water from
entering the pipes.
When using conventional (R22)
flare tools to flare R410A pipes, the
dimension A should be approxi-
mately 0.5 mm more than indicated
in the table (for flaring with R410A
flare tools) to achieve the speci-
fied flaring. Use a thickness gauge
to measure the dimension A. It is
recommended that a R410A flaring
tool is used.
4.3.2. Bending pipes
• If pipes are shaped by hand, be careful not to collapse them.
• Do not bend the pipes in an angle more than 90°.
• When pipes are repeatedly bend or stretched, the material will harden, making it difficult
to bend or stretch them anymore.
• Do not bend or stretch the pipes more than 3 times.
To prevent breaking of the pipe, avoid sharp bends.
If the pipe is bent repeatedly at the same place, it will break.
4.3.3. Pipe connection
Be sure to install the pipe against the port on the indoor unit and the outdoor unit cor-
rectly. If the centering is improper, the flare nut cannot tightened smoothly. If the flare
nut is forced to turn, the threads will be damaged.
Do not remove the flare nut from the indoor unit pipe until immediately before connect-
ing the connection pipe.
Do not use mineral oil on flared part. Prevent mineral oil from getting into the system as
this would reduce the lifetime of the units.
Hold the torque wrench at its grip, keeping it at a right angle with the pipe, in order to
tighten the flare nut correctly.
(1) Detach the caps and
plugs from the pipes.
(2) Center the pipe against
the port on the indoor
unit, and then turn the
flare nut by hand.
(3) When the flare nut is tightened properly
by your hand, hold the body side coupling
with a separate spanner, then tighten with
a torque wrench. (See the table below for
the flare nut tightening torques.)
Flare nut
[mm (in)]
6.35 (1/4) dia.
9.52 (3/8) dia.
12.70 (1/2) dia.
15.88 (5/8) dia.
19.05 (3/4) dia.
Die
Pipe
Dimension A
Pipe outside
[mm]
diameter
(Flare tool for
[mm (in)]
R410A, clutch
type)
6.35 (1/4)
9.52 (3/8)
12.70 (1/2)
0 to 0.5
15.88 (5/8)
19.05 (3/4)
Pipe outside
Width across
diameter
flats of Flare nut
[mm (in)]
6.35 (1/4)
9.52 (3/8)
12.70 (1/2)
15.88 (5/8)
19.05 (3/4)
CAUTION
CAUTION
Connection pipe
(Liquid)
Tightening torque
[N·m (kgf·cm)]
Torque
wrench
16 to 18 (160 to 180)
32 to 42 (320 to 420)
49 to 61 (490 to 610)
Indoor unit pipe
63 to 75 (630 to 750)
(Body side)
90 to 110 (900 to 1,100)
Check if [L] is
flared uniformly
and is not cracked
or scratched.
Dimension
0
B
[mm]
-0.4
9.1
13.2
16.6
19.7
24.0
Width across
flats
[mm]
17
22
26
29
36
Connection pipe (Gas)
Tighten with 2
wrenches.
Holding
wrench
Flare nut
Connection pipe
En-4