Refrigerant circuit address setting
(25)
Make sure the
function number is
"02". Refer to (15).
Press the "TIMER
"TIMER set (-)"
set (-)" button.
•
Press the "RESET" button to cancel the address setting mode.
(Example) ADDRESS : 25
OPERATION LAMP
(GREEN)
0.5sec ON / 0.5sec OFF
TIMER LAMP
(ORANGE)
2 times
0.5sec ON / 0.5sec OFF
FILTER LAMP
(RED)
5 times
■
Setting up each indoor unit
Repeat steps (1) through to (25). Steps (1) through to (6) and (21) to (25)
only need to carried out if the custom code is different to the factory setting
of "A".
■
Reset the power after setting up address of all indoor units
Important
•
If the reset is not performed, address cannot be read in normally.
•
After all the addresses have been set, the circuit breaker needs to be
switched off for at least 2 minutes.
After the 2 minutes has passed, power can be restored.
•
The set address is stored in the PC board and will remain in memory even
when the power is turned off.
However setting address is effective after power reset. Record the
address set in the indoor unit on a label,
etc., and affi x the label to the unit so it can be used for
after-sales service operations.
* Address 0 setting will not indicate TIMER LAMP and FILTER LAMP.
* Once the "RESET" button is pressed on the remote
controller, the OPERATION MODE will be set in the
"AUTO MODE".
Please adjust the OPERATION MODE to either "COOLING" or "HEATING"
before trying to operate the air conditioner.
* Note : If CUSTOM CODE is set to anything other than "A", the remote
controller must be set accordingly to the INDOOR UNIT setting.
1sec ON / 1sec OFF
1 - 10 sec
1 - 10 sec
6. FUNCTION SETTING
•
This procedure changes to the function settings used to control the indoor
unit according to the installation conditions. Incorrect settings can cause the
indoor unit malfunction.
•
After the power is turned on, perform the "FUNCTION SETTING"
according to the installation conditions using the remote controller.
•
The settings may be selected between the following 2: Function Number
or Setting Number.
•
Settings will not be changed if invalid numbers or setting numbers are
selected.
■
Preparation
(1) Turn on the power to the indoor unit.
* By turning on the power indoor units initializes EEV, so make sure
the piping air-tight test and vacuuming have been conducted before
turning on the power.
* Also check again to make sure no wiring mistakes were made before
turning on the power.
Breaker ON
20A
■
Switching selection of function setting mode
(2) Press and hold the "MANUAL/AUTO" button for 3 seconds.
OPERATION
indicator (Green)
LAMP
IR RECEIVER
UNIT
(3) Press and hold the "FAN" and the "SET TEMP.
holding these 2 buttons, press the "RESET" button.
FAN
SET TEMP. ( )
RESET
•
The position of the "MANUAL/AUTO" button varies depending on the
model. Refer to the operation manual for the position that is included with
the unit.
•
The error will be displayed by continuously pressing the "MANUAL/AUTO"
for 10 sec or more. In this case, release the button or turn off the power.
■
Selection and confi rmation of custom code
(4) Press the "SET TEMP.
" or
"SET TEMP.
" buttons to
select the custom code that
matches the setting with the
indoor unit. By selecting the
appropriate custom code,
the communication between
the indoor unit and the wire-
less RC become possible.
Indoor
Indoor
units
units
Pi Pi Pi
MANUAL
AUTO
MANUAL AUTO
" buttons. Whilst
Function setting
mode display
CUSTOM CODE
( - - - )
The initial setting is " "