Carlin 701CRD Manual de instruções de instalação e funcionamento - Página 3

Procurar online ou descarregar pdf Manual de instruções de instalação e funcionamento para Queimador Carlin 701CRD. Carlin 701CRD 9 páginas. Oil burners

Carlin 701CRD Manual de instruções de instalação e funcionamento
FIRING BOILERS WITH COMBUSTION
CHAMBERS
The Models 701CRD and 801CRD operate with superior efficiency
and cleanliness in properly designed refractory-type combustion
chambers. Very wide tolerance to burner adjustments and other
variables is found when these chambers are used.
Tables 1 and 2, show the recommended minimum inside
dimensions for refractory brick, refractory pre-cast and
TABLE 1 701CRD

MINIMUM DIMENSIONS RECOMMENDED IN REFRACTORY

COMBUSTION CHAMBERS–(Inches)
1
2
3
High Fire
Oil
Delivery
Rate
GPH @
Length
Width
150 PSI
L
W
6.00
19
13.5
6.60
22
14.0
7.20
24
14.5
7.80
27
15.0
8.40
30
15.5
9.00
33
15.5
9.60
34
16.0
10.20
35
16.0
10.80
36
16.0
11.40
37
16.5
12.00
48
16.5
12.60
52
16.5
13.20
55
16.5
Note: These are MINIMUM dimensions and each may be exceeded without much effect.
TABLE 2 801CRD
MINIMUM DIMENSIONS RECOMMENDED IN REFRACTORY
COMBUSTION CHAMBERS–(Inches)
1
2
3
High Fire
Oil
Delivery
Rate
GPH @
Length
Width
150 PSI
L
W
11.4
33
15
12.0
34
16
12.6
35
16
13.2
36
17
13.2
38
17
14.4
39
18
15.0
40
18
15.6
41
19
16.2
43
19
16.8
44
20
17.4
46
20
18.0
47
21
18.6
49
21
19.2
51
22
19.8
52
22
Note: These are MINIMUM dimensions and each may be exceeded without much effect.
Refer to Fig. 2 for details showing L, C & H.
FIRING BOILERS WITHOUT REFRACTORY CHAMBERS
Depending upon the geometry of the combustion space some units perform better than others without refractory. When the
back wall of the unit coincides approximately with the end ofthe flame, a target of refractory material is usually required.
Tables 3 and 4 show MINIMUM dimensions required for good combustion. They may be exceeded without much effect.
4
5
6
Minimum
Suggested
Dia.
Dimens.
Height
Vertical
C
H
Cyl.
7.0
13
17
7.0
14
20
7.5
14
24
7.5
15
25
8.0
15
28
8.0
15
31
8.0
16
32
8.0
16
33
8.0
16
34
8.5
16
35
8.5
16
46
8.5
16
50
8.5
16
53
4
5
6
Minimum
Suggested
Dia.
Dimens.
Height
Vertical
C
H
Cyl.
7.5
15
31
8.0
16
32
8.0
16
33
8.5
17
34
8.5
17
36
9.0
18
37
9.0
18
38
9.5
19
39
9.5
19
41
10.0
20
42
10.0
20
44
10.5
21
45
10.5
21
47
11.0
22
49
11.0
22
50
pre-formed refractory fiber chambers. Due to their quick
warm-up properties, the light, insulating-type materials
are slightly preferable although these burners show less
dependence upon refractory temperature than previous
models. Refractory materials in boilers and furnaces should
be capable of withstanding 2600°F (1427°C) or higher.
The notes accompanying Table 1 and 2 provide further
details relative to variations in dimensions and geometry.
TABLE 3 701CRD

MINIMUM DIMENSIONS RECOMMENDED BOILERS FIRED

WITHOUT COMBUSTION CHAMBERS–(Inches)
1
2
High Fire
Oil
Delivery
Rate
L
GPH @
With
150 PSI
Target
6.00
19
6.60
22
7.20
24
7.80
27
8.40
30
9.00
33
9.60
34
10.20
35
10.80
36
11.40
37
12.00
48
12.60
52
13.20
55
TABLE 4 801CRD
MINIMUM DIMENSIONS RECOMMENDED BOILERS FIRED
WITHOUT COMBUSTION CHAMBERS–(Inches)
1
2
High Fire
Oil
Delivery
Rate
L
GPH @
With
150 PSI
Target
11.4
33
12.0
34
12.6
35
13.2
36
13.8
38
14.4
39
15.0
40
15.6
41
16.2
43
16.8
44
17.4
46
18.0
47
18.6
49
19.2
51
19.8
52
Refer to Figs. 3 and 4 for details showing L, C & D
3
3
4
5
L
Withou
Width
Dimens.
Target
W
C
23
15.5
8.0
26
16.0
8.0
28
16.5
8.5
32
17.0
8.5
35
17.5
9.0
38
17.5
9.0
40
18.0
9.0
41
18.0
9.0
42
18.0
9.0
43
18.5
9.5
54
18.5
9.5
58
18.5
9.5
60
16.5
9.5
3
4
5
L
Withou
Width
Dimens.
Target
W
C
38
17
7.5
39
18
8.0
40
18
8.0
41
19
8.5
43
19
8.5
44
20
9.0
46
20
9.0
47
21
9.5
49
21
9.5
50
22
10.0
52
22
10.0
54
23
10.5
56
23
10.5
58
24
11.0
59
24
11.0
6
Dimens.
D
10.0
10.0
10.5
10.5
11.0
11.0
11.0
11.0
11.0
11.5
11.5
11.5
11.5
6
Dimens.
D
9.5
10.0
10.0
10.5
10.5
11.0
11.0
11.5
11.5
12.0
12.0
12.5
12.5
13.0
13.0