Carlin 60200FR Manual de instruções de instalação e funcionamento - Página 5

Procurar online ou descarregar pdf Manual de instruções de instalação e funcionamento para Controlador Carlin 60200FR. Carlin 60200FR 9 páginas. Gas burner primary control
Também para Carlin 60200FR: Manual de instruções de instalação e funcionamento (8 páginas)

Carlin 60200FR Manual de instruções de instalação e funcionamento
SETTING
MODE
OPTIONS
PRESS THE
BUTTONS
TO
CHANGE
SETTINGS
Shaded box = default setting.
** MA Code ("N" models) are non-recycling and will lock out on flame failure.
**Changing this setting to 'Yes', with limits powered will exit Settings mode and result in immediate 'Call For Heat'.
If flame is sensed during Pre-Purge, control will lockout immediately (except when Pre-Purge is set to 0 seconds).
*
• Pre-Purge: Time period motor and ignitor are on prior to Trial
for Ignition. Note: If flame is sensed during Pre-Purge, control
will lockout immediately (except when Pre-Purge is set to 0 or 3
seconds).
• Trial for Ignition: Flame-establishing period during ignition.
• Post-Purge: Time period the motor is on after the Call for Heat is
satisfied to allow for evacuation of combustion gases. A call for
heat during Post-Purge will result in a recycle.
• Allowed Recycles: Number of Recycles allowed during a single
Call for Heat prior to lockout.
Carlin Combustion Technology, Inc.
A V A I L A B L E
PRESS THE
BUTTON TO VIEW DIFFERENT SETTING MODES
Trial for
Pre -Purge
Post-Purge
Ignition
0 Sec
4 Sec
0 Sec
10 Sec
6 Sec
10 Sec
30 Sec
15 Sec
90 Sec
30 Sec
60 Sec
2 min

Setup Menu Definitions

S E T T I N G S
TT
Allowed
Jumpered
Recycles
Internal**
None*
Yes
1
No
3
• TT Jumpered Internal: Allows TT to be "jumpered" by software
program.
• Clear Fault History: Allows all prior burner fault conditions stored
in control to be cleared.
• Restore Factory Defaults: Allows all factory defaults to be
restored in control (refer to settings shaded in gray in the table
above). Will reset and reboot control .
5
Restore
Clear Fault
Factory
History
Defaults
Yes
Yes
No
No
MN60200FR1 070319