Formula Air BADA000013 Manual de manutenção - Página 4

Procurar online ou descarregar pdf Manual de manutenção para Unidade de controlo Formula Air BADA000013. Formula Air BADA000013 18 páginas. Atex non-return valve

Formula Air BADA000013 Manual de manutenção
1.1

How it works

During the normal process, the non‐return valve's flap remains opened due to the airflow
(Figure: 2). At deadlock, the valve closes due to the flap's own weight.
When an explosion takes place, the ATEX certified non‐return valve blocks the expansion of the
explosion due to the front spreading pressure along the ductwork (Figure: 3).
After an explosion and due to pressure oscillations, the valve could re‐open. To avoid the re‐
opening, a safety lock system keeps the valve closed long enough to avoid the propagation of
flames during the explosion event, as can be seen in Figure: 4. The locking system consists of a
spring metal that allows it to bend easily. Therefore, if the flap closes the arm hits the locking
system and the top of the locking system will give in. This way, the flap gets locked beneath the
top plate of the locking system. Once the explosion is completely over, the lock must be
Figure: 2 Non‐Return Valve in open airflow configuration
Figure: 3 Non‐Return Valve in closed configuration
3