Anden A100 Manual de instruções de instalação e funcionamento - Página 7

Procurar online ou descarregar pdf Manual de instruções de instalação e funcionamento para Desumidificador Anden A100. Anden A100 16 páginas.

Anden A100 Manual de instruções de instalação e funcionamento

LEVELING

The feet can be adjusted to level the unit and
accommodate drain fittings and secondary condensate
pans as required . Refer to top mounted bubble level
and adjust feet until bubble is within the outer circle .
Leveling is required to ensure proper drainage from
the dehumidifier . See FIGURE 8 .

CONDENSATE PAN, CONDENSATE PUMP AND FLOAT SWITCH

A condensate pan is recommended when suspending
the dehumidifier over the canopy . Adhere to local
codes regarding draining of the condensate pan . If a
condensate pump is needed, install it in the condensate
pan as well .
Install a condensate overflow safety switch (i . e . float
switch) in the condensate pan, remove the factory
installed jumper wire between the Float Switch
terminals on the control and wire the float switch to the
dehumidifier as shown in FIGURE 9 . Overflow safety
switches on condensate pumps can be wired to the
Float Switch terminals in a similar fashion .
FIGURE 8 – LEVEL THE UNIT
0.38" MIN
2.00" MAX
3/4" DRAIN
FIGURE 9 – FLOAT SWITCH WIRING
BUBBLE LEVEL
NORMALLY CLOSED
FLOAT SWITCH
90-2592
90-1857
7