Anderson 70G600 Manual de operação - Página 14
Procurar online ou descarregar pdf Manual de operação para Queimador Anderson 70G600. Anderson 70G600 16 páginas.
Not enough gas: Gas valve is not open, Not
enough gas. Air in the gas line
The low fire flame is
Low fire adjusted too slow
weak or unstable
Not enough gas
Incorrect air flow setting
The burner goes off
Insufficient air (flame too rich)
when it cycles to
high fire
The burner is erratic
Flame signal weak
and does not
Internal damage to the burner. Some parts
respond to
inside the burner may be loose or dirty.
adjustment
The burner is
The air/gas ratio is out of adjustment
unstable or produces
soot or smoke
Cannot achieve full
Air filter is blocked
capacity
Gas pressure is too low into the main gas
pressure regulator
Increase furnace/chamber pressures Poor
piping practices
Anderson Thermal Soluions(Suzhou)Co. Ltd.
Anderson Thermal Solutions – ANX70 Burner Operation Manual
12
Check wiring to the automatic gas shut-off
valve. Check output from the flame
safeguard. Open gas cock. Purge gas line.
Increase low fire gas setting. Check start-up
settings and adjust to increase low gas flow.
Check start-up settings. Investigate any
change, i.e. blocked filter, loose connections
Check start-up settings. Check air filter, clean
or replace if required
Check condition of flame monitoring device.
Contact Anderson Thermal Solutions (Suzhou)
Co., Ltd.
Measure all gas pressures and air pressures.
Compare to initial start-up settings, and
adjust them where necessary
Clean or replace the air filter.
Adjust gas pressure.
Re-check setup pressures
Contact Anderson