Anderson VFC86 Manual de operação - Página 6
Procurar online ou descarregar pdf Manual de operação para Queimador Anderson VFC86. Anderson VFC86 12 páginas.
Number
Name
1
Duct
3
Gas channel
5
Downstream pressure test point
7
Side plate
9
Air distributes sheet metal
VFS86 Series Burner has a separated ignition burner of maximum capacity 50 kW. The user
needs to supply combustion air with an oxygen content of 21% for the ignition burner, so,
a small air blower or compressed air needs to apply to ignition burner. According to ignition
burner's manual, 5mbar combustion air and 3mbar gas pressure is necessary for ignition
burner operation continually. The pressure above means in a neutral environment, if oven
chamber pressure exists, chamber pressure needs to be added to the pressure value above.
It should be noted that the depth of ignition burner extended to the main burner is
adjustable according to site requirement. The ignition burner diagram is shown in Fig 2.
Anderson Thermal Soluions(Suzhou)Co., Ltd
Anderson Thermal Solutions – VFC86 Burner Operation Manual
Fig 1 VFC86 Burner Diagram
Number
2
4
Upstream pressure test point
6
Pilot burner
8
Fig 2 ignition burner
4
Name
Damper
Nozzle