Anderson EVA2 Series Instruções de instalação e de utilização

Procurar online ou descarregar pdf Instruções de instalação e de utilização para Controlador Anderson EVA2 Series. Anderson EVA2 Series 2 páginas.

The Series EVA2 and EVA3 Electric Actuators are designed to mount directly
onto the Series GV globe valves, creating a complete, low cost, and compact
control valve package. Floating or modulating control inputs are available, and the
24 VAC synchronic motor includes a magnetic clutch to protect the motor in stall
conditions. Actuators are ruggedly constructed with a fire-proof ABS housing and
robust aluminum bracket. Features include a visual position indicator and manual
override to make this actuator an excellent choice for any size area, large or small.
FEATuRES
• Manual override
• Compact size
• Floating control or selectable 0-10 VDC or 4-20 mA proportional control
• Reversible direction on proportional models
• Magnetic clutch protects motor in stall conditions
Actuator
Output
Model
Action
Force
EVA2F
Floating
225 lb
(1000 N)
EVA2M
Modulating
225 lb
(1000 N)
EVA3F
Floating
337 lb
(1500 N)
EVA3M
Modulating
337 lb
(1500 N)
W.E. ANDERSON DIV., DWYER INSTRuMENTS, INC.
P.O. BOX 358 • MICHIGAN CITY, INDIANA 46360 u.S.A.
Series EVA2 and EVA3 Electric Actuators
Specifications - Installation and Operating Instructions
Valve
Compatible
Size
Valve Models
1˝ to 2-1/2˝
GV2__ , GV3__
1˝ to 2-1/2˝
GV2__ , GV3__
1˝ to 2-1/2˝
GV2__, GV3__
1˝ to 2-1/2˝
GV2__, GV3__
Ø4-1/32
KNOB
POWER
CONNECT
CONNECTOR
SPECIFICATIONS
SERIES EVA2, EVA3
Output Force: EVA2: 225 lb (1000 N); EVA3: 337 lb (1500 N).
Power Requirements: 24 VAC.
Power Consumption: EVA2F (EVA3F): 5.5 VA; EVA2M (EVA3M): 7.5 VA.
Cycle Time: EVA2F (EVA2M): 97 sec/in. (3.8 sec/mm); EVA3F (EVA3M): 164
sec/in. (6.45 sec/mm).
Enclosure Rating: IP40.
Housing Material: Fire-proof ABS plastic (UL94V-0).
Bracket Material: Aluminum.
Operating Temperature: 36 to 131°F (2 to 55°C).
Storage Temperature: -4 to 149°F (-20 to 65°C).
Humidity Limit: <90%, non-condensing.
Electrical Connection: Screw terminal.
Modulating Input: 0 to 10 VDC or 4 to 20 mA.
Weight: EVA2F (EVA3F): 2.43 lb (1.1 kg); EVA2M (EVA3M): 3.31 lb (1.15 kg).
INSTALLATION
1. Tightly screw the valve connector on the valve body. Please pay attention to the
direction of the connector.
2. Install the actuator bracket on the valve connector.
3. Insert the U-type connector into the bracket, and lock the connector nut.
4. Lift up the valve stem and put the lock nut and indicator guide onto it, then
rotate the connecting rod of the actuator and let it rotate onto the valve stem.
Use spanner to lock the locknut after adjusted into position.
5. In vertical installations, leave enough head room to unscrew the actuator prior
to servicing the valve body.
6. Wire the unit according to the appropriate Wiring Diagram.
Phone: 219/879-8000
Fax: 219/872-9057
Bulletin V-8
[102.4]
4-57/64
[124.22]
3-15/16
[100]
www.dwyer-inst.com