GENERATOR START CONTROL MODULE
APPLICATION 1 - ELECTRIC START HI SPEED GAS/PROPANE GENERATOR W/ STARTER CONTROL BOX
This application matches most high speed or portable generator sets that have an electric starter and some type of starter control.
These generators should have the ignition switch left in the 'on' position. The start commands usually come through the GSCM
connected to the remote start terminals. The remote start may be either momentary or maintained.
The K2 (crank) relay is used to switch the start input which is looking for a momentary signal. The K2 (crank) relay opens when
the generator has reached 30Hz, or half speed. If this setting doesn't allow the start input to remain engaged long enough for the
generator to stay on-line, adjust the run disconnect setting to 55Hz (see Section-4 for changing adjustments). The K4 (shutdown)
relay provides a momentary "stop" signal until the generator AC Hz has dropped to zero.
The K3 (ignition) relay provides a continuous run signal for
generators requiring a "maintained" start signal. The K4
(shutdown) relay provides a momentary "stop" signal until
the generator AC Hz has dropped to zero.
ATKINSON ELECTRONICS, INC.
Web Site: www.atkinsonelectronics.com
A double pole "kill switch" wired and installed by the user
stops the generator instantly in emergency situations such as
a fuel spill. One switch pole (N.C.) kills power to the GSCM
opening all relays. The other switch pole (N.O.) shorts out
the magneto for an instant stop.