Compact Electric CDMR-61 Manual do utilizador - Página 12
Procurar online ou descarregar pdf Manual do utilizador para Relés Compact Electric CDMR-61. Compact Electric CDMR-61 13 páginas. Digital line monitoring relay
Line Monitoring Relay CDMR-61
Tab.1:
Type:
CDMR-61
U(rated): ...........
Plant:
Date:
Note: The voltage setting ranges and values are listed below in % of the rated voltage.
Par.
Funct.
No.
92, 94
U<<<
96
U<<<
97
U<<<
Return Delay
93, 95
U<<<
91
U<<<
Output Relay
22, 24
U<<
26
U<<
27
U<<
Return Delay
23, 25
U<<
21
U<<
Output Relay
15, 17
U<
19
U<
20
U<
Return Delay
16, 18
U<
14
U<
Output Relay
8, 10
U>
12
U>
13
U>
Return Delay
9, 11
U>
7
U>
Output Relay
1, 3
U>>
5
U>>
6
U>>
Return Delay
2, 4
U>>
0
U>>
Output Relay
50
f<<
54
f<<
55
f<<
Return Delay
51
f<<
50
f<<
Output Relay
CDMR61e_man_A1.doc
/ User Manual
V AC
The CDMR displays these values in [Volt].
Setting
Parameter
range
TripVoltage
[10 - 130%] Un
Trip Delay
[0.04 - 60] s
[0.04 - 60] s
Hysteresis
[0 - 20%] Un
K1 ..K5
TripVoltage
[10 - 130%] Un
Trip Delay
[0.04 - 60] s
[0.04 - 60] s
Hysteresis
[0 - 20%] Un
K1 ..K5
TripVoltage
[10 - 130%] Un
Trip Delay
[0.04 - 60] s
[0.04 - 60] s
Hysteresis
[0 - 20%] Un
K1 ..K5
TripVoltage
[10 - 130%] Un
Trip Delay
[0.04 - 60] s
[0.04 - 60] s
Hysteresis
[0 - 20%] Un
K1 ..K5
TripVoltage
[10 - 130%] Un
Trip Delay
[0.04 - 60] s
[0.04 - 60] s
Hysteresis
[0 - 20%] Un
K1 ..K5
Trip Frequ
[45 -65] Hz
Trip Delay
[0.06 - 60] s
[0.06 - 60] s
Hysteresis
[0 – 5.00] Hz
K1 ..K5
Serial-Nr:
Cubicle:
Default
setting
70% Un
0.1s
0.1s
3%
--
70% Un
0.1s
0.1s
3%
(Schaltpkt)
--
80% Un
0.1s
0.1s
3%
(Schaltpkt)
--
110% Un
0.1s
0.1s
3%
(Schaltpkt)
--
120% Un
0.1s
0.1s
3%
(Schaltpkt)
--
49,00 Hz
0.12s
0.12s
0.05 Hz
--
Page 12
Customers
setting value
Dim
V
s
s
V
V
s
s
V
V
s
s
V
V
s
s
V
V
s
s
V
Hz
s
s
Hz