Daikin VRVIII Series Manual de dados técnicos - Página 11
Procurar online ou descarregar pdf Manual de dados técnicos para Ar condicionado Daikin VRVIII Series. Daikin VRVIII Series 20 páginas. Air conditioning systems bs box
Também para Daikin VRVIII Series: Manual de dados técnicos (18 páginas), Manual de dados técnicos (20 páginas), Manual de dados técnicos (11 páginas)
9
Sound data
9 - 1 Sound pressure spectrum
FXUQ71MA
3
Approximate
threshold hearing for
continuous noise
NOTES
1
Over all (dB):
2
Power level (dB):
3
Measuring place: Anechoic chamber
4
Operating conditons:
•
Power source: 230V 50Hz
•
Cooling: Return air temperature: 27C DB, 19C WB; Outdoor temperature: 35C DB, 24C WB
•
Heating: Return air temperature: 20C DB, 15C WB; Outdoor temperature: 7C DB, 6C WB
5
Directions discharge
6
Location of microphone
7
Operating noise differs with operation and ambient conditions.
FXUQ125MA
Approximate
threshold hearing for
continuous noise
NOTES
1
Over all (dB):
2
Power level (dB):
3
Measuring place: Anechoic chamber
4
Operating conditons:
•
Power source: 230V 50Hz
•
Cooling: Return air temperature: 27C DB, 19C WB; Outdoor temperature: 35C DB, 24C WB
•
Heating: Return air temperature: 20C DB, 15C WB; Outdoor temperature: 7C DB, 6C WB
5
Directions discharge
6
Location of microphone
7
Operating noise differs with operation and ambient conditions.
10
• Indoor Units • 4-WAY BLOW CEILING SUSPENDED CASSETTE • FXUQ-MAV1
4D014037D
HI (230V)
Low (230V)
Octave band center frequency (Hz)
Scale
230V
Hi
Low
A
40
35
230V
Hi
Low
56
51
230V
1m
4D0140039D
HI (230V)
Low (230V)
Octave band center frequency (Hz)
Scale
230V
Hi
Low
A
44
39
230V
Hi
Low
60
55
230V
1m
®
• VRV
Systems • Indoor Units
FXUQ100MA
Approximate
threshold hearing for
continuous noise
Octave band center frequency (Hz)
NOTES
1
Over all (dB):
Scale
A
2
Power level (dB):
230V
Hi
59
3
Measuring place: Anechoic chamber
4
Operating conditons:
•
Power source: 230V 50Hz
•
Cooling: Return air temperature: 27C DB, 19C WB; Outdoor temperature: 35C DB, 24C WB
•
Heating: Return air temperature: 20C DB, 15C WB; Outdoor temperature: 7C DB, 6C WB
5
Directions discharge
230V
6
Location of microphone
1m
7
Operating noise differs with operation and ambient conditions.
4D0140038D
HI (230V)
Low (230V)
50 Hz 240V
Hi
Low
43
38
Low
54