Atlantic Boilers MULTI-ELEC STANDARD 210 Manual técnico - Página 7

Procurar online ou descarregar pdf Manual técnico para Caldeira Atlantic Boilers MULTI-ELEC STANDARD 210. Atlantic Boilers MULTI-ELEC STANDARD 210 17 páginas.

2.3) Essential accessories

The following items are required :-
A. One 4-bar safety valve and one 7-bar temperature and pressure relief valve
B. One shunt pump – protected by overloads (1A to 1.6A adjustable) and run/fault lamps
C. One water flow switch
Recommended water flow settings in litres per second
-
Pipeline sizes
Minimum range
Maximum setting
D. One automatic air vent with isolating valve
E. One drain ball valve

2.4) Precautions

The Multi-elec Standard requires an installation conforming to
89.336/EEC Directive (electromagnetic compatibility)
73/23/EEC Directive (low voltage)
92/42/EEC Directive (performance)
The ATLANTIC Guarantee conditions

2.5) Boiler room arrangements

The Multi-elec Standard must be installed
In an adequately-ventilated boiler room with ambient temperature below 30degC
And relative humidity maintained between 30% and 80% and where condensation
does not occur
In a non-corrosive atmosphere
In a non-explosive atmosphere
Where there is good access to the boiler position for installation and maintenance
Where there is good access for delivery, off-loading and positioning
Using similar materials in the pipework, and avoiding materials leading to electrolytic
action and system deterioration
The Multi-elec Standard is not suitable for external installation

2.6) Commissioning

The boiler must be completely full of water before the heating elements are switched
on. To ensure 100% filling, manual and automatic vents must be in effective positions
where complete air clearance can be guaranteed.
The boiler can be filled with water by connecting a fill hose to the boiler drain valve
and partly opening the valve.
The boiler safety valve can also be used firstly to vent the boiler at filling and,
secondly, ensuring the blow-down facility of the valve is clear in case of emergency.
For full guarantee, the boiler should be commissioning by Atlantic 2000 or an
authorised engineer
32mm
40mm
0.35-0.47 0.53-0.72 0.61-0.83
1.0
1.6
7
50mm
65mm
1.0-1.4
1.9