Atlantic Ultraviolet AeroLogic AERO-20 Manual do Proprietário - Página 11
Procurar online ou descarregar pdf Manual do Proprietário para Equipamento de laboratório Atlantic Ultraviolet AeroLogic AERO-20. Atlantic Ultraviolet AeroLogic AERO-20 16 páginas.
U
, L
Q
NIT
AMP AND
!
WARNING:
Always disconnect power to the unit before performing any service or maintenance.
!
CAUTION:
Ultraviolet lamp and quartz sleeve are easily damaged and may cause injury if broken.
Exercise care when handling.
1. Disconnect power to the HVAC system.
2. Using mounting hub, mark the centers (locations) of the four (4) 3/32" pilot holes and the 1 1/4" center hole.
Also see "Figure 5 - AERO Mounting Cutout" on page 9.
!
CAUTION:
Wear protective gloves when working on or around duct sheet metal.
3. Drill the appropriate holes as indicated on the mounting pattern. Remove burrs and sharp edges where possible.
4. Install the gasket and mounting hub to the duct using the supplied No. 8-18 x 3/4" mounting hardware.
5. Install lamp. The lamp socket is located inside the threaded end of the AeroLogic
pins with lamp socket. Carefully press lamp pins into the socket until lamp is seated against the socket.
6. Moisten a clean, lint-free cloth with denatured alcohol and wipe the lamp.
7. Install quartz sleeve.
a. Place o-ring approximately 3/4" to 1" from the open end of the quartz sleeve.
b. Carefully slide the quartz sleeve over the lamp, into the threaded base. The quartz sleeve will rest against
a shoulder in the mounting base. Slide the o-ring down until it is seated against the angled face of the base.
®
c. Slide the Teflon
d. Slide the nut over the quartz sleeve and tighten firmly (by hand only). Do not use hand tools! Tightening with
hand tools is likely to cause quartz sleeve to break.
8. Moisten a clean, lint-free cloth with denatured alcohol and wipe the quartz sleeve.
®
9. Fit AeroLogic
to the mounting hub, and tighten until secure.
®
10. Plug AeroLogic
into properly grounded, electrical outlet.
11. Restore power to the HVAC system.
!
Germicidal ultraviolet rays are harmful to the eyes and skin.
12. Verify operation by viewing lamp, use of personal protection equipment is required. If the unit is not operating
properly, go to "Troubleshooting" section on page 13.
13. While wearing protective eye wear, inspect HVAC system for any ultraviolet light leakage. No ultraviolet light
should be visible from any duct opening, joint, seam, etc. The installation can also be inspected using a sensitive
ultraviolet meter, to insure that the ultraviolet radiant exposure of personnel is within acceptable limits. If
necessary, seal any openings, joints, seams, etc. using aluminum tape or equivalent ultraviolet resistant material.
(See "Zenith™ Ultraviolet Meter" in the "Optional Accessories" section on page 12.)
S
I
UARTZ
LEEVE
NSTALLATION
Mechanical hazard. Duct sheet metal has sharp edges.
Figure 4 - Lamp & Quartz Sleeve Installation
washer over the quartz sleeve until it is resting against the o-ring.
WARNING:
Avoid exposure to direct or strongly reflected germicidal ultraviolet rays.
,
O
REPLACEMENT
R
®
base. To install; line up lamp
C
LEANING
11