Atlantic Ultraviolet AeroLogic AERO-44 Manual do Proprietário - Página 6

Procurar online ou descarregar pdf Manual do Proprietário para Equipamento de laboratório Atlantic Ultraviolet AeroLogic AERO-44. Atlantic Ultraviolet AeroLogic AERO-44 16 páginas.

Atlantic Ultraviolet AeroLogic AERO-44 Manual do Proprietário

INSTALLATION

U
P
NIT
LACEMENT
Proper unit placement is essential. To ensure safe and effective operation, the location should:
Have enough duct width to mount unit with lamp perpendicular to airflow, with the longest duct length for
increased exposure time.
Be on the supply air plenum, LOCATION A (preferred), or on the return air plenum, LOCATION B (alternate).
See Figure 1- Unit Replacement.
Be able to support the weight of the AeroLogic
the weight, the duct must be re-enforced, to support the weight, before installing.
Have a properly grounded, electrical outlet within reach of the unit's power supply cord.
Not be mounted under any source of moisture or condensation, such as humidifiers, cooling coils, etc.
Not be mounted near any duct openings, joints, seams, etc. If necessary, seal all openings, joints, seams, etc. using
aluminum tape or equivalent ultraviolet resistant material.
Prevent exposure of any plastic, rubber or other non-metallic materials, with inadequate resistance to ultraviolet,
such as; plastic drain pans, wiring insulation, flex ducts, humidifiers, filters etc. If necessary, shield all plastic,
rubber or other non-metallic parts using aluminum tape, conduit, sheet metal or equivalent ultraviolet resistant
material.
Be free of any components that would be damaged by or interfere with the installation.
Be easily accessible for viewing lamp operation through the sight glass assembly.
Be easily accessible and allow enough clearance for routine cleaning or maintenance.
Be downstream from air filters. Dust particles will reduce the effectiveness of the unit.
6
®
unit. If the duct construction does seem capable of supporting
Figure 1 - Unit Placement