Anly H3C-R11 Manual do utilizador

Procurar online ou descarregar pdf Manual do utilizador para Temporizador Anly H3C-R11. Anly H3C-R11 6 páginas. Multi-function analogue timer

Meraserw-5 s.c. 70-312 Szczecin , ul.Gen.J.Bema 5 , tel.(91)484-21-55 , fax (91)484-09-86 , e-mail: [email protected] , www.meraserw.szczecin.pl
H3C-R8 / H3C-R11
MULTI-FUNCTION
ANALOGUE TIMER
User's Manual
RESTRICTIONS ON USE
When using this product in applications
that require particular safety or when
using this product in important facilities,
please pay attention to the safety of the
overall system and equipment. Install fail-
safe mechanisms, perform redundancy
checks and periodic inspections and
adopt other appropriate safety measures
when it is necessary. This product is rated
at Class Ⅱ
.

SPECIFICATIONS

AC/DC : 24~240V
Operating voltage
Allowable operating
85 ~ 110% of rated operating voltage
voltage range
Rated frequency
50 / 60Hz
Contact rating
250VAC 5A (Resistive load)
Reset time
MAX 0.1s
Approx. 3VA
Power consumption
Life
Mechanical : 5,000,000 times / Electrical : 100,000 times
o
Ambient temperature
-10~+50
C
Ambient humidity
MAX 85% RH
Weight
Approx. 100g
BASIC SETTING
Mode Selector
Setting Operation Mode
Turn the Mode Selector with a screwdriver in either
clockwise or counter-clockwise direction until the
desired operation mode (A, A
, B, B
, B
, C, E, or J) is visible through the Mode Window. Make sure
4
3
4
the selector snaps into a secured position, not between two modes.
Setting Time Scale
Turn the Scale Selector with a screwdriver and the time scale will cycle through all values.
Stop when the desired scale range (1.2, 3, 12, 30) and the scale unit (sec, min, hrs, 10h) are visible
through the Scale Range Windows and the Scale Unit Window respectively.
Clockwise turns increment the time scale; counter-clockwise turns decrement the scale.
Make sure the selector snaps into a secured position, not between two scales.
A
: ON delay (2C)
t
Rt
SOURCE (2-7)
N.C. (1-4, 8-5)
N.O. (1-3, 8-6)
OUTPUT LED
POWER LED
Set time = t , t - a < t , Reset time = Rt
A
4 : ON delay (1A1C)
t
Rt
SOURCE (2-7)
N.C. (8-5)
N.O. (8-6)
OUTPUT LED
N.C. (1-4)
N.O. (1-3)
POWER LED
Set time = t , t - a < t , Reset time = Rt
B
: Repeat cycle OFF start (2C)
t
t
t - a Rt
t
SOURCE (2-7)
N.C. (1-4, 8-5)
N.O. (1-3, 8-6)
OUTPUT LED
POWER LED
Set time = t , t - a < t , Reset time = Rt
SAFETY PRECAUTION
WARNING
CAUTION
‧Note this incorrect wiring of this product can damage it and lead to other hazards. Make sure the product has
been correctly wired before turning the power ON.
‧Before wiring, or removing / mounting the product, be sure to turn the power OFF. Failure to do so might cause
electric shock.
‧Do not touch electrically charged parts such as the power terminals. Doing so might cause electric shock.
‧Do not disassemble the product. Doing so might cause electric shock or faulty operation.
‧Use the product within the operating ranges recommended in the specification (temperature, humidity, voltage,
shock, mounting direction, atmosphere etc.). Failure to do so might cause fire or faulty operation.
‧Firmly tighten the wires to the socket. Insufficient tightening of the wires to the socket might cause fire.
A
Mode Window
Groove for
screwdriver
Scale Selector
TIMING CHART(Output mode) for H3C-R 8
B
3 : Repeat cycle ON start (1A1C)
t
Rt
t - a
SOURCE (2-7)
N.C. (8-5)
N.O. (8-6)
OUTPUT LED
N.C. (1-4)
N.O. (1-3)
POWER LED
Set time = t , t - a < t , Reset time = Rt
B
4 : Repeat one shot output (1A1C)
t
Rt
t - a
SOURCE (2-7)
N.C. (8-5)
N.O. (8-6)
OUTPUT LED
N.C. (1-4)
N.O. (1-3)
POWER LED
Set time = t , t - a < t , Reset time = Rt
C
: Interval (2C)
t
t
SOURCE (2-7)
N.C. (1-4, 8-5)
N.O. (1-3, 8-6)
OUTPUT LED
POWER LED
Set time = t , t - a < t , Reset time = Rt
P r o d u c t i s s u b j e ct t o c h a n g e w i t h o u t n o t i c e .
This manual uses the following symbols to ensure safe operation of this timer.
Warnings are indicated when mishandling this product might result in death or serious injury
to user.
Cautions are indicated when mishandling this product might result in minor injury to the user,
or only physical damage to the timer.
WARNING
CAUTION
NAMES AND FUNCTIONS OF FACEPLATE
LEDs
POWER: Power indicator(Flashes
when Timer operates; lit when
Timer stops operating)
OUT: Output indicator(Lit when
output is ON)
Time Dial
H3C-R 8
4
5
3
2
1
8
SOURCE
t
t
t - a Rt
t
t
t
t
t
t - a
Rt
t
t
0.6s
0.6s
0.6s
0.6s
t
Rt
t
Rt
t - a
POWER
MODE
Mode Window
OUT
A
15
Mode Selector
10
20
5
25
Scale Range Windows
0
30
sec
Scale Selector
H3C-R
ANLY
Scale Unit Window
CONNECTION
H3C-R11
6
7
E
: Interval (1A1C)
t
Rt
SOURCE (2-7)
N.C. (8-5)
N.O. (8-6)
OUTPUT LED
N.C. (1-4)
N.O. (1-3)
POWER LED
Set time = t , t - a < t , Reset time = Rt
J
:
One shot output (1A1C)
t
Rt
SOURCE (2-7)
N.C. (8-5)
0.5s
N.O. (8-6)
OUTPUT LED
N.C. (1-4)
N.O. (1-3)
POWER LED
Set time = t , t - a < t , Reset time = Rt
6
5
7
4
8
3
9
2
10
1
11
SOURCE
t
Rt
t - a
t
Rt t - a
0.5s