corresponding marked voltage. For example if the voltage source is
55V AC rms then only the 50V indicator LED band will illuminate, if
700V AC rms all four indicator LED bands will illuminate.
Note: The individual LED indications are not to be used for
measuring purposes.
3.3 Operating Duty Ratio
The voltage indicator should be operated (ON) for a maximum
period of 30 seconds. This should be followed by a recovery period
(OFF) of 4 minutes.
The operating duty ratio is 8 to 1, so if the voltage indicator is only
ON for 2 seconds then the OFF period need only be 16 seconds.
3.4 Proving Check
Before each use the voltage indicator should be examined for
damage, cracks, cuts or scratches to the housing, cable and prods.
The cable has black outer and contrasting inner insulation, to allow
damage to the cable to be easily identified. If there is any doubt the
voltage indicator should not be used.
Before and after use, verify the voltage indicator is functioning
correctly with a proving device (PD440S or PD440SRD for MTL10.
PD690S or PD690SRD for MTL15.), or a known good voltage
source. Do not use the voltage indicator if any expected voltage
indication LED's fail to illuminate correctly during proving.
8